Terminal
block
Side panel
Cord clamp
Conduit hole
Power supply cable
(1Ø, 208-230V)
Connecting cable
(1Ø, 208/230V)
Taping
(for sealing)
Lock nut
(field supply)
Conduit
(field supply)
Conduit panel
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
Screw
Control Access
Panel
Power Wiring (208-230V) and Communications Cable Details
Figure 307:Example of Power Wiring and Communications Cable Terminations.Find the outdoor unit terminal block by unscrewing the
control access panel.
Side panel of the outdoor unit has knockout holes for
the conduits. After install is complete, seal up any gaps
between the panel and the conduits.
Clamp is included near the terminal block to help protect
the connections from strain on the cables.
Always have a trained technician properly ground
the outdoor unit. If the outdoor unit is not properly
grounded, there is a risk of electric shock.
Use a conduit for the power wiring.
The communications cable should be separated and
isolated from the outdoor unit power wiring, comput-
ers, radio and television broadcasting facilities, as
well as medical imaging equipment.
WIRING CONNECTIONS
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
WIRING CONNECTIONS | 217
Wiring Connections