Multi F Outdoor Condenser Installation Manual

MULTI
F
MAX
MULTI
F
10
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 2: Multi F Outdoor Unit Electrical Data.
GENERAL DATA
Multi F Outdoor Unit Electrical Data
Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP LRA
Com-
pressor
Quantity
Compressor
Motor RLA
Outdoor Fan Motor
Indoor
Fan
Motor
kW FLA FLA
1.5 LMU183HV
60 208 - 230 187 - 253
15.8 20 16.0 1 12.0 0.085 0.40 0.40
2 LMU243HV 16.0 20 16.0 1 12.0 0.085 0.40 0.60
2.5 LMU303HV 18.4 25 19.0 1 13.5 0.124 0.73 0.80
3 LMU363HV 18.4 25 19.0 1 13.5 0.124 0.73 0.80
Maximum Overcurrent Protection (MOP) is calculated as follows:
/DUJHVWPRWRU)/$[6XPRIRWKHUPRWRU)/$URXQGHGGRZQ
to the nearest standard fuse size.
Indoor Fan Motor (FLA; Full Load Amps [A]) is based on the following
indoor unit combinations:.
- 18,000 ODU (LMU183HV): 9k Wall Mounted IDU x 2
2'8/08+9N:DOO0RXQWHG,'8[N:DOO
Mounted IDU x 1
- 30,000 ODU (LMU303HV): 9k Wall Mounted IDU x 4
- 36,000 ODU (LMU363HV): 9k Wall Mounted IDU x 4
*Wall Mounted IDU FLA is 0.2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance
is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
LRA = (Locked Rotor Amps)