Multi F Outdoor Condenser Installation Manual

62
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
ELECTRICAL
LG Terminal Connections
LG uses a “JIS” type of screw for all terminals; use a JIS screwdriver to tighten and
loosen these screws and avoid damaging the terminal. Do not over tighten the
connections — over tightening will damage the terminals — but firmly and securely at-
tach the wiring in a way to prevent external forces from being imparted to the terminal
block.
7KHWHUPLQDOVODEHOHG³*1'´DUH127JURXQGWHUPLQDOV7KHWHUPLQDOVODEHOHG
ARE ground terminals.
3RODULW\PDWWHUV$OZD\VFRQQHFW³$´WR³$´DQG³%´WR³%´
Always create a wiring diagram that contains the exact sequence in which all the indoor units and branch distribution units (Multi F MAX
V\VWHPVRQO\DUHZLUHGLQUHODWLRQWRWKHRXWGRRUXQLW
Do not include splices or wire nuts in the communication cable.
Figure 77: JIS Screws.
$OZD\VKDYHDWUDLQHGVHUYLFHSURYLGHUSURSHUO\JURXQGWKHRXWGRRUXQLW,IWKHRXWGRRUXQLWLVQRWSURSHUO\JURXQGHGWKHUHLVDULVNRIHOHF-
WULFVKRFNUHVXOWLQJLQSK\VLFDOLQMXU\RUGHDWK
3URYLGHDFLUFXLWEUHDNHUEHWZHHQWKHSRZHUVRXUFHDQGWKHRXWGRRUXQLW)DLOXUHWRGRVRZLOOFDXVHERGLO\LQMXU\RUGHDWK
Multi F and Multi F MAX systems operate at 1Ø, 208-230V, 60Hz, and power is wired
to the outdoor unit only. The outdoor unit will supply power to the indoor units and the
branch distribution units (Multi F MAX systems only) through the communication / con-
nection (power) cable.
Power supply to the outdoor unit must be selected based on NEC and local codes. Maxi-
mum allowable voltage fluctuation ±10% or nameplate rated value.
Power wiring to the outdoor unit(s) must be solid or stranded, and must comply with all
local and national electrical codes.
Properly ground the outdoor unit and indoor unit per NEC and local codes.
Ground wire must be longer than the common power / communication wires.
Connect the wiring firmly so the wires cannot be easily pulled out.
Refer to the inside of the chassis cover or control cover for circuit and terminal block
diagrams.
Always match color codes of each wire and follow wiring diagram.
Do not install power wiring to the outdoor unit and the communication / connection (power) cable to the indoor unit in the same conduit.
Use separate conduits.
3RZHU6XSSO\3RZHU:LULQJ6SHFLILFDWLRQV
Air
Conditioner
Main Power Source
Circuit Breaker
Use a circuit breaker
or time delay fuse
Figure 78: Circuit BreakerTable 32: Circuit Breaker / Fuse Size.
7/16" ± 1/8"
13/16
"
GN/YL
Power Wiring, Ground
to Outdoor Unit
Figure 79: Multi F / Multi F MAX Outdoor Unit
Power Wiring.
&RQQHFWLRQVDQG6SHFL¿FDWLRQV
Outdoor Unit Model Power Source
Fuse or Breaker
Capacity
LMU183HV, LMU243HV 1Ø, 208-230V 20A
LMU303HV, LMU363HV 1Ø, 208-230V 25A
LMU481HV, LMU541HV 1Ø,208-230V
40A
LMU601HV 1Ø, 208-230V