FINAL INSTALLATION PROCEDURES
Forced Cooling Operation Function
Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit
PCB is ON (indicates indoor units are in
forced cooling operation).
5. Add refrigerant.
,IWKHJUHHQ/('OLJKWRQWKHRXWGRRUXQLW3&%LV21LWLQGLFDWHVWKHFRPSUHVVRULV2))GXH
to low pressure in the system.
7XUQ',36ZLWFKWR2))DIWHUILQLVKLQJ1RUPDO2SHUDWLRQVHWWLQJ
Only the first four DIP switches are used to set settings and functions.
Location of DIP Switches on Multi F and Multi F MAX Outdoor Units
Figure 113: Multi F Outdoor Unit DIP Switch Locations.
Figure 114: LMU183-243-303-363HV
Forced Cooling DIP Switch Setting.
12 43
12 43
ON
OFF
5
5
Figure 115: LMU481-541-601HV
Forced Cooling DIP Switch Setting.
1234
56
ON
OFF
LMU183HV (18 kBtu/h) and LMU243HV (24 kBtu/h)
Main PCB
Sub PCB LMU243HV (24 kBtu/h)
Tact Switch
DIPSW1
DIPSW1
Tact Switch
Sub PCB LMU183HV (18 kBtu/h)
LMU303HV (30 kBtu/h) and LMU363HV (36 kBtu/h)
Inverter PCB
Sub PCB
DIPSW
Tact
Switch
LMU601HV (60 kBtu/h)
Tact Switch
DIPSW
LMU481HV (48 kBtu/h) and LMU541HV (54 kBtu/h)
Tact Switch
DIPSW