Final Installation Procedures
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
',36ZLWFK6HWWLQJVIRU2SWLRQDO0RGHV
FINAL INSTALLATION PROCEDURES
Wiring Error Check
Use to verify if wiring is properly installed.
1. Shut power down to the system.
2. Set DIP Switch 2 to ON.
3. Turn power on to the system.
4. Check if the Red and Green LEDs on the outdoor unit PCB are ON
(indicate indoor units are in forced operation mode).
5. If the wiring is correctly installed, the Green LED will light up. If the wiring is in-
correctly installed, the Red and Green LEDs will blink, indicating which part of the
system is in error.
Red LED = Piping Number
Green LED = Wiring Number (Room)
Example: If the Red LED blinks twice and the Green LED blinks three times, the second
piping to the third room is in error (see at right).
,IWKHLQGRRUXQLWVDUHQRWFRPPXQLFDWLQJSURSHUO\WRWKHRXWGRRUXQLWWKH:LULQJ
Error Check cannot operate correctly.
Only the part of the system in error will be displayed. System will operate correctly
after the error is fixed.
,IRXWGRRUDQGLQGRRUWHPSHUDWXUHVDUHWRRORZH[ZLQWHUWKHZLULQJHUURUFKHFNIXQFWLRQZLOOQRWRSHUDWH5HG/('LV21
Turn DIP Switch 2 to OFF after finishing (Normal Operation setting).
Only the first four DIP switches are used to set settings and functions.
Reducing Power Consumption
Enables more efficient system operation by reducing the maximum power consumption
value (reducing the MCA).
1. Shut power down to the system.
2. For Step 1, set only DIP Switch 3 to ON.
3. For Step 2, set only DIP Switch 4 to ON.
4. Turn power on to the system.
Table 39: Reducing Power Consumption Current Levels.
Phase
Model
Multi F
LMU183HV,
LMU243HV
Multi F
LMU303HV,
LMU363HV
Multi F MAX
LMU481HV,
LMU541HV,
LMU601HV
Step 1 (A) 91322
Step 2 (A) 81121
Power
Consumption
and Current
Normal
Time
One (1)
Second
LED 1
(Red)
LED 2
(Green)
Three (3)
Blinks
Two (2)
Blinks
One (1)
Second
One (1)
Second
One (1)
Second
Two (2)
Blinks
Three (3)
Blinks
Figure 118: Wiring Error Check Example.
Step 1 Step 2
Figure 119: Reducing Power Consumption Chart.
Reduced Power Consumption reduces outdoor unit capacity.
2QO\WKH¿UVWIRXU',3VZLWFKHVDUHXVHGWRVHWVHWWLQJVDQGIXQFWLRQV
Figure 116: LMU183-243-303-
363HV Wiring Error Check DIP
Switch Setting.
Figure 117: LMU481-541-601HV
Wiring Error Check DIP Switch
Setting.
1234
56
ON
OFF
Figure 120: LMU183-243-303-363HV Reducing Power Consumption
DIP Switch Settings.
Figure 121: LMU481-541-601HV Reducing Power Consumption DIP
Switch Settings.
1234
56
ON
OFF
1234
56
ON
OFF
Step 1 Step 2
12 43
12 43
ON
OFF
5
5
12 43
12 43
ON
OFF
5
5
12 43
12 43
ON
OFF
5
5