Multi F Four-Way Ceiling Cassette Service Manual

- 58 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 5. Trouble Shooting
Display
code
Title Cause of error Check point & Normal condition
22
AC Input current is higher
than the limit.
• Input voltage error(low
voltage)
• Over load operation
(Outdoor fan constraint,
screened, blocked)
• Burned parts inside PCB
• Check input voltage
• Check outdoor fan canstraint / screened / flow
structure
• Check PCB current sensor parts
5V_GND5V_GND5V_GND
DC_LINK
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.