Multi F Four-Way Ceiling Cassette Service Manual

Part 5. Trouble Shooting
- 81 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
23
DC Link High / Low Volt
• DC Link Voltage is
above 420Vdc
• DC Link Voltage is
below 140Vdc
• Check CN_(L), CN_(N) Connection
• Check Input Voltage
• Check PCB DC Link voltage sensor parts
Display
code
Title Cause of error Check point & Normal condition
Error Diagnosis and Countermeasure Flow Chart
Is Inverter PCB assembly
Power connection normal?
No
Check connection from terminal block to
Inverter PCB assembly CN(L), CN(N)
Yes
Is input voltage normal ?
No
Yes
Is Inverter PCB Normal?
No
Replace inverter PCB assembly
Recheck power and installation
condition
Yes
Check L~N Voltage is 230V±15%
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state