Multi F Installation Manual

11
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
ELECTRICAL DATA
Nominal
Tons
Unit Model
No.
Hertz Voltage Phase
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Fan Motor
Indoor
Fan
Motor
kW FLA FLA
1.5 LMU18CHV
60 208 - 230 1 187 - 253
13.3 20 1 8.9 0.09 0.59 1.60
2 LMU24CHV 14.3 20 1 9.4 0.09 0.59 2.00
2.5 LMU30CHV 16.6 25 1 10.8 0.12 0.73 2.40
3 LMU36CHV 17.9 25 1 11.2 0.12 0.73 3.20
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
Indoor Fan Motor (FLA) is based on the maximum combina-
tion of indoor units.
The max combination for each outdoor unit is:
- 18,000 ODU (LMU18CHV): 12,000 IDU x 2
- 24,000 ODU (LMU24CHV): 12,000 IDU x 2 + 9,000 IDU
x 1
- 30,000 ODU (LMU30CHV): 12,000 IDU x 3
- 36,000 ODU (LMU36CHV): 12,000 IDU x 4
Table 4: Multi F Outdoor Unit Electrical Data.
Nominal
Tons
Unit Model
No.
Hertz Voltage Phase
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Condenser Fan Motor(s)
Indoor
Fan
Motor
Condenser
Fan Quantity
x kW
Condenser
Fan Motor
FLA
4.0 LMU480HV 60 208 - 230
1
187 - 253 27.3 40 1 17.5 2 x 0.12 0.73 x 2 4.0
4.5 LMU540HV 60 208 - 230 187 - 253 29.4 40 1 18.5 2 x 0.12 0.73 x 2 4.8
5.0 LMU600HV 60 208 - 230 187 - 253 32.2 45 1 20.4 2 x 0.12 0.73 x 2 5.2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
Indoor Fan Motor (FLA) is based on the maximum combina-
tion of indoor units.
The max combination for each outdoor unit is:
- 48,000 ODU (LMU480HV): 12,000 IDU x 5
- 54,000 ODU (LMU540HV): 12,000 IDU x 6
- 60,000 ODU (LMU6000HV): 12,000 IDU x 6 + 9,000 IDU
x 1
Table 5: Multi F MAX Electrical Data.
Multi F and Multi F MAX Outdoor Units