Multi F Outdoor Unit Engineering Manual

PERFORMANCE DATA
Rated Cooling Combination Tables
Table 118: LMU540HV with Ducted Indoor Units — Rated Cooling Combination Table.
Total Indoor Unit Capacity
(kBtu/h)
Cooling Capacity Input (W)
EER SEERMinimum Rated Maximum
Minimum Rated Maximum
Btu/h kW Btu/h kW Btu/h kW
24 13,600 3.99 22,667 6.64 25,076 7.35 1,000 1,550 2,337 14.60 18.3
25 14,167 4.15 23,611 6.92 26,121 7.66 1,168 1,668 2,434 14.20 18.1
26 14,733 4.32 24,556 7.20 27,165 7.96 1,251 1,787 2,532 13.70 18.1
27 15,300 4.48 25,500 7.47 28,210 8.27 1,334 1,905 2,629 13.40 18.0
28 15,867 4.65 26,444 7.75 29,255 8.57 1,518 2,023 2,726 13.10 17.9
29 16,433 4.82 27,389 8.03 30,300 8.88 1,606 2,142 2,824 12.80 17.8
30 17,000 4.98 28,333 8.30 31,345 9.19 1,695 2,260 2,921 12.50 17.7
31 17,567 5.15 29,278 8.58 32,390 9.49 1,855 2,378 3,019 12.30 17.7
32 18,133 5.31 30,222 8.86 33,434 9.80 1,947 2,497 3,116 12.10 17.6
33 18,700 5.48 31,167 9.13 34,479 10.11 2,040 2,615 3,213 11.90 17.5
34 19,267 5.65 32,111 9.41 35,524 10.41 2,132 2,733 3,311 11.70 17.4
35 19,833 5.81 33,056 9.69 36,569 10.72 2,281 2,852 3,408 11.60 17.3
36 20,400 5.98 34,000 9.96 37,614 11.02 2,376 2,970 3,505 11.40 17.3
37 20,967 6.14 34,944 10.24 38,659 11.33 2,471 3,088 3,603 11.30 17.2
38 21,533 6.31 35,889 10.52 39,703 11.64 2,565 3,207 3,700 11.20 17.1
39 22,100 6.48 36,833 10.80 40,748 11.94 2,660 3,325 3,798 11.10 17.0
40 22,667 6.64 37,778 11.07 41,793 12.25 2,755 3,443 3,895 11.00 16.9
41 23,233 6.81 38,722 11.35 42,838 12.56 2,849 3,562 3,992 10.90 16.8
42 23,800 6.98 39,667 11.63 43,883 12.86 2,944 3,680 4,090 10.80 16.8
43 24,367 7.14 40,611 11.90 44,927 13.17 3,039 3,798 4,187 10.70 16.7
44 24,933 7.31 41,556 12.18 45,972 13.47 3,133 3,917 4,284 10.60 16.6
45 25,500 7.47 42,500 12.46 47,017 13.78 3,228 4,035 4,382 10.50 16.5
46 26,067 7.64 43,444 12.73 48,062 14.09 3,323 4,153 4,479 10.50 16.4
47 26,633 7.81 44,389 13.01 49,107 14.39 3,417 4,272 4,576 10.40 16.4
48 27,200 7.97 45,333 13.29 50,152 14.70 3,512 4,390 4,674 10.30 16.3
49 27,767 8.14 46,278 13.56 51,196 15.00 3,607 4,508 4,771 10.30 16.2
50 28,333 8.30 47,222 13.84 52,241 15.31 3,701 4,627 4,869 10.20 16.1
51 28,900 8.47 48,167 14.12 53,286 15.62 3,796 4,745 4,966 10.20 16.0
52 29,467 8.64 49,111 14.39 54,331 15.92 3,891 4,863 5,063 10.10 16.0
53 30,033 8.80 50,056 14.67 55,376 16.23 3,985 4,982 5,161 10.00 15.9
54 30,600 8.97 51,000 14.95 56,421 16.54 4,080 5,100 5,258 10.00 15.8
55 30,981 9.08 51,161 14.99 56,777 16.64 4,105 5,131 5,290
10.00 15.8
56 31,362 9.19 51,322 15.04 57,134 16.75 4,129 5,161 5,321 9.90 15.8
57 31,743 9.30 51,483 15.09 57,491 16.85 4,154 5,192 5,353 9.90 15.8
58 32,125 9.42 51,644 15.14 57,848 16.95 4,178 5,223 5,385 9.90 15.8
59 32,506 9.53 51,805 15.18 58,205 17.06 4,203 5,254 5,416 9.90 15.8
60 32,887 9.64 51,966 15.23 58,561 17.16 4,228 5,284 5,448 9.80 15.8
61 33,268 9.75 52,127 15.28 58,918 17.27 4,252 5,315 5,480 9.80 15.8
62 33,649 9.86 52,288 15.32 59,275 17.37 4,277 5,346 5,512 9.80 15.8
63 34,030 9.97 52,449 15.37 59,632 17.48 4,301 5,377 5,543 9.80 15.8
64 34,412 10.09 52,611 15.42 59,989 17.58 4,326 5,407 5,575 9.70 15.8
65 34,793 10.20 52,772 15.47 60,346 17.69 4,351 5,438 5,607 9.70 15.8
66 35,174 10.31 52,933 15.51 60,702 17.79 4,375 5,469 5,638 9.70 15.8
67 35,555 10.42 53,094 15.56 61,059 17.90 4,400 5,500 5,670 9.70 15.8
68 35,936 10.53 53,255 15.61 61,416 18.00 4,424 5,530 5,702 9.60 15.8
69 36,317 10.64 53,416 15.66 61,773 18.10 4,449 5,561 5,733 9.60 15.8
70 36,699 10.76 53,577 15.70 62,130 18.21 4,474 5,592 5,765 9.60 15.8
71 37,080 10.87 53,738 15.75 62,486 18.31 4,498 5,623 5,797 9.60 15.8
72 37,461 10.98 53,899 15.80 62,843 18.42 4,523 5,653 5,828 9.50 15.8
73 37,842 11.09 54,060 15.84 63,200 18.52 4,547 5,684 5,860 9.50 15.8
1
Capacity as rated: 0 ft. above sea level with Piping Length as Main Pipe (16.4 ft.) + Branch pipe
(98.4 ft.) = 115 ft.
0 ft. level difference between outdoor and indoor units.
2
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
3
Wiring cable size must comply with the applicable local and national codes.
4
The specification may be subject to change without prior notice for purpose of improvement.
5
Sum of connected indoor units capacity is 24~73 kBtu/h.
6
At least two indoor units should be connected.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
132 | MULTI F MAX OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual