Multi F Outdoor Unit Engineering Manual

Table 128: LMU540HV Cooling Capacity Table — Non-Ducted (continued) / Ducted Indoor Units.
Combination
Capacity Index
(kBtu/h[%])
Outdoor Air
Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC PI TC PI TC PI TC PI TC PI TC PI
Non-Ducted
Indoor Units
24 (40%)
14 22.87 0.97 24.29 1.01 25.71 1.04 26.74 1.05 28.55 1.07 29.97 1.10
20 22.85 0.98 24.27 1.02 25.69 1.06 26.72 1.07 28.53 1.09 29.95 1.11
25 22.84 1.00 24.25 1.03 25.67 1.07 26.70 1.08 28.51 1.10 29.93 1.13
30 22.82 1.01 24.24 1.05 25.65 1.09 26.68 1.10 28.49 1.12 29.90 1.14
35 22.80 1.03 24.22 1.06 25.63 1.10 26.66 1.11 28.46 1.14 29.88 1.16
40 22.78 1.04 24.20 1.08 25.61 1.12 26.63 1.13 28.44 1.15 29.86 1.17
45 22.77 1.05 24.18 1.09 25.59 1.13 26.61 1.14 28.42 1.17 29.83 1.19
50 22.75 1.07 24.16 1.11 25.57 1.15 26.59 1.16 28.40 1.18 29.81 1.21
55 22.73 1.08 24.14 1.12 25.55 1.16 26.57 1.18 28.38 1.20 29.79 1.22
60 22.71 1.10 24.12 1.14 25.53 1.18 26.55 1.19 28.36 1.21 29.77 1.24
65 22.70 1.11 24.11 1.15 25.51 1.19 26.53 1.21 28.33 1.23 29.74 1.25
70 22.68 1.12 24.09 1.16 25.50 1.21 26.51 1.22 28.31 1.24 29.72 1.27
75 22.13 1.18 23.54 1.23 24.94 1.27 25.96 1.29 27.75 1.31 29.16 1.34
80 21.59 1.24 22.99 1.29 24.39 1.34 25.40 1.35 27.19 1.38 28.59 1.41
85 21.05 1.31 22.44 1.35 23.84 1.40 24.85 1.42 26.64 1.44 28.04 1.47
90 20.51 1.37 21.90 1.42 23.29 1.47 24.30 1.48 26.08 1.51 27.48 1.54
95 19.92 1.43 21.31 1.48 22.69 1.53 23.33 1.55 25.47 1.58 26.86 1.61
100 19.43 1.49 20.82 1.54 22.21 1.60 23.03 1.62 24.98 1.65 26.37 1.68
105 18.95 1.55 20.34 1.60 21.72 1.66 22.73 1.68 24.50 1.71 25.89 1.75
110 18.46 1.61 19.85 1.67 21.24 1.73 22.24 1.75 24.01 1.78 25.40 1.82
115 17.98 1.67 19.37 1.73 20.75 1.79 21.76 1.81 23.53 1.85 24.92 1.88
118 17.69 1.71 19.07 1.77 20.46 1.83 21.46 1.85 23.24 1.89 24.63 1.93
122 17.59 1.75 18.98 1.82 20.37 1.88 21.37 1.91 23.14 1.94 24.53 1.98
Ducted Indoor
Units
73 (135%)
14 52.99 3.55 56.29 3.68 59.58 3.82 61.95 3.86 66.16 3.94 69.45 4.01
20 52.95 3.61 56.24 3.74 59.53 3.87 61.91 3.92 66.11 3.99 69.40 4.07
25 52.91 3.66 56.20 3.79 59.49 3.93 61.86 3.97 66.06 4.05 69.35 4.13
30 52.87 3.71 56.16 3.84 59.44 3.98 61.81 4.03 66.01 4.10 69.29 4.19
35 52.83 3.76 56.11 3.90 59.40 4.04 61.77 4.08 65.96 4.16 69.24 4.25
40 52.79 3.81 56.07
3.95 59.35 4.09 61.72 4.14 65.91 4.22 69.19 4.30
45 52.75 3.86 56.03 4.00 59.30 4.15 61.67 4.20 65.86 4.27 69.13 4.36
50 52.71 3.91 55.99 4.05 59.26 4.20 61.62 4.25 65.81 4.33 69.08 4.42
55 52.67 3.96 55.94 4.11 59.21 4.26 61.58 4.31 65.76 4.39 69.03 4.48
60 52.63 4.01 55.90 4.16 59.17 4.31 61.53 4.36 65.71 4.44 68.97 4.53
65 52.59 4.07 55.86 4.21 59.12 4.37 61.48 4.42 65.66 4.50 68.92 4.59
70 52.55 4.12 55.81 4.27 59.08 4.42 61.43 4.47 65.60 4.56 68.87 4.65
75 51.29 4.34 54.54 4.50 57.80 4.66 60.15 4.71 64.31 4.80 67.56 4.90
80 50.02 4.56 53.27 4.73 56.52 4.90 58.86 4.96 63.01 5.05 66.26 5.15
85 48.77 4.78 52.01 4.96 55.25 5.14 57.59 5.20 61.73 5.29 64.97 5.40
90 47.51 5.00 50.75 5.19 53.98 5.38 56.31 5.44 60.44 5.54 63.67 5.65
95 46.15 5.23 49.37 5.42 52.58 5.62 54.06 5.68 59.02 5.79 62.23 5.90
100 45.03 5.45 48.25 5.65 51.46 5.85 53.36 5.92 57.89 6.03 61.11 6.15
105 43.91 5.67 47.12 5.88 50.34 6.09 52.66 6.16 56.77 6.28 59.98 6.40
110 42.78 5.89 46.00 6.11 49.21 6.33 51.54 6.40 55.64 6.52 58.86 6.66
115 41.66 6.11 44.87 6.34 48.09 6.57 50.41 6.65 54.52 6.77 57.74 6.91
118 40.98 6.25 44.20 6.48 47.41 6.71 49.74 6.79 53.85 6.92 57.06 7.06
122 40.76 6.43 43.97 6.66 47.19 6.90 49.51 6.98 53.62 7.11 56.84 7.26
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with Piping Length as Main Pipe (16.4 ft.) + Branch
pipe (98.4 ft.) = 115 ft.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these
values can be different if the system is not running consistently.
PERFORMANCE DATA
Cooling Capacity Tables
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
142 | MULTI F MAX OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual