Multi F Outdoor Unit Engineering Manual

Combination
Capacity Index
(kBtu/h[%])
Outdoor Air
Temp.
Indoor Air Temp. °F DB
61 64 68 70 72 75
°F DB °F WB TC PI TC PI TC PI TC PI TC PI TC PI
Non-Ducted
Indoor Units
59 (110%)
0 -0.4 27.12 3.44 25.50 3.57 25.53 3.62 24.94 3.65 24.47 3.68 23.44 3.81
5 4.5 32.66 3.59 31.13 3.72 30.68 3.80 30.03 3.84 29.51 3.87 28.32 4.00
10 9 36.37 3.73 34.90 3.86 34.13 3.96 33.43 4.01 32.88 4.06 31.58 4.18
17 15 40.46 3.92 39.05 4.05 37.92 4.17 37.18 4.24 36.59 4.30 35.18 4.42
20 19 42.93 4.05 41.56 4.17 40.22 4.32 39.45 4.40 38.83 4.46 37.36 4.58
25 23 47.05 4.27 45.66 4.39 44.07 4.56 43.24 4.65 42.57 4.72 40.97 4.85
30 28 51.19 4.51 49.60 4.66 47.90 4.80 47.02 4.90 46.32 4.99 44.61 5.11
35 32 55.32 4.75 53.56 4.92 51.73 5.04 50.80 5.16 50.06 5.25 48.25 5.38
40 36 58.14 4.88 56.50 5.05 54.70 5.20 53.75 5.31 53.00 5.39 51.08 5.54
45 41 61.66 5.06 60.19 5.23 58.41 5.39 57.44 5.49 56.67 5.57 54.61 5.73
47 43 63.07 5.13 61.66 5.30 59.90 5.47 58.92 5.56 58.14 5.64 56.02 5.80
50 46 63.26 5.09 61.98 5.25 60.45 5.40 59.57 5.48 58.87 5.55 56.88 5.69
55 51 63.56 5.04 62.51 5.17 61.36 5.29 60.65 5.35 60.09 5.40 58.31 5.51
60 56 63.87 4.99 63.04 5.08 62.27 5.18 61.73 5.22 61.31 5.25 59.74 5.33
63 59 64.06 4.95 63.36 5.03 62.81 5.11 62.38 5.14 62.04 5.16 60.60 5.22
68 64 64.24 4.92 63.68 4.99 63.36 5.04 63.04 5.06 62.78 5.07 61.47 5.11
Non-Ducted
Indoor Units
54 (100%)
0 -0.4 26.69 3.34 25.10 3.47 25.13 3.52 24.55 3.55 24.09 3.57 23.07 3.70
5 4.5 32.15 3.49 30.64 3.62 30.20 3.69 29.56 3.73 29.05 3.76 27.87 3.89
10 9 35.80 3.63 34.36 3.75 33.60 3.84 32.91 3.90 32.36 3.94 31.09 4.06
17 15 39.82 3.81 38.44 3.93 37.33 4.05 36.60 4.12 36.01 4.17 34.63 4.30
20 19 42.26 3.93 40.91 4.05 39.60 4.19 38.83 4.27 38.23 4.33 36.77 4.45
25 23 46.32 4.15 44.94 4.27 43.38 4.43 42.56 4.52 41.90 4.59 40.33 4.71
30 28 50.39 4.38 48.83 4.52 47.15 4.66 46.28 4.76 45.59 4.85 43.92 4.97
35 32 54.45 4.61 52.72 4.77 50.93 4.90 50.01 5.01 49.28 5.10 47.50 5.23
40 36 57.23 4.74 55.62 4.91 53.85 5.05 52.92 5.15 52.17 5.24 50.28 5.38
45 41 60.70 4.91 59.25 5.08 57.50 5.23 56.55 5.33 55.78 5.41 53.76 5.56
47 43 62.09 4.98
60.70 5.14 58.96 5.31 58.00 5.40 57.23 5.47 55.15 5.64
50 46 62.27 4.95 61.01 5.10 59.50 5.24 58.64 5.32 57.95 5.39 55.99 5.53
55 51 62.57 4.90 61.53 5.02 60.40 5.14 59.70 5.19 59.15 5.24 57.40 5.35
60 56 62.88 4.84 62.06 4.94 61.29 5.03 60.77 5.07 60.35 5.10 58.81 5.17
63 59 63.06 4.81 62.37 4.89 61.83 4.96 61.41 4.99 61.07 5.01 59.65 5.07
68 64 63.24 4.78 62.69 4.84 62.37 4.90 62.05 4.91 61.80 4.92 60.51 4.96
Non-Ducted
Indoor Units
49 (90%)
0 -0.4 24.22 3.01 22.78 3.12 22.80 3.17 22.28 3.19 21.86 3.21 20.93 3.33
5 4.5 29.17 3.14 27.81 3.25 27.40 3.32 26.82 3.36 26.36 3.39 25.29 3.50
10 9 32.49 3.26 31.17 3.38 30.49 3.46 29.87 3.51 29.37 3.55 28.21 3.66
17 15 36.14 3.43 34.88 3.54 33.88 3.65 33.21 3.71 32.68 3.76 31.42 3.87
20 19 38.35 3.54 37.12 3.65 35.93 3.77 35.24 3.84 34.69 3.90 33.37 4.01
25 23 42.03 3.73 40.78 3.84 39.36 3.98 38.62 4.06 38.02 4.13 36.59 4.24
30 28 45.72 3.94 44.31 4.07 42.78 4.19 42.00 4.29 41.37 4.36 39.85 4.47
35 32 49.41 4.15 47.84 4.30 46.21 4.41 45.38 4.51 44.72 4.59 43.10 4.70
40 36 51.93 4.27 50.47 4.42 48.86 4.54 48.02 4.64 47.34 4.71 45.62 4.84
45 41 55.08 4.42 53.76 4.57 52.18 4.71 51.31 4.80 50.62 4.87 48.78 5.01
47 43 56.34 4.48 55.08 4.63 53.50 4.78 52.63 4.86 51.93 4.93 50.04 5.07
50 46 56.50 4.45 55.36 4.59 53.99 4.72 53.21 4.79 52.58 4.85 50.81 4.98
55 51 56.78 4.41 55.84 4.51 54.81 4.62 54.18 4.67 53.67 4.72 52.08 4.82
60 56 57.05 4.36 56.31 4.44 55.62 4.52 55.14 4.56 54.76 4.59 53.36 4.66
63 59 57.22 4.33 56.60 4.40 56.11 4.47 55.72 4.49 55.42 4.51 54.13 4.56
68 64 57.39 4.30 56.88 4.36 56.60 4.41 56.31 4.42 56.08 4.43 54.90 4.47
PERFORMANCE DATA
Heating Capacity Tables
Table 141: LMU540HV Heating Capacity Table — Non-Ducted Indoor Units (continued).
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal Capacity as rated: 0 ft. above sea level with Piping Length as Main Pipe (16.4 ft.) + Branch
pipe (98.4 ft.) = 115 ft.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
MULTI F MAX OUTDOOR UNIT | 155
Multi F MAX Outdoor Unit Data
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.