Multi F Outdoor Unit Engineering Manual

INSTALLATION & LAYOUT BEST PRACTICES
Refrigerant Piping System Layout
Multi F MAX Outdoor Unit System Piping Connections
Branch Distribution to Indoor Unit Piping Connections
•Install indoor unit liquid and vapor refrigerant pipes (and connection wiring) to the appropriate branch distribution ports.
•Clearly note on the indoor unit’s refrigerant piping (liquid, vapor) which branch distribution port it is connected to (A, B, C, D).
Outdoor Unit Piping Connections LMU540HV
Liquid Line Connection (in., OD) x Qty. 3/8 x 1
Vapor Line Connection (in., OD) x Qty. 3/4 x 1
Avoid Pipe Damage
When routing field-provided piping, avoid damaging the outdoor unit from excessive vibration.
Correctly route the piping so it does not make contact with mounting bolts. Allow room for field installation.
Properly insulate the liquid and gas lines separately up to the point of connection at the unit frame.
See Table 181 for Multi F MAX outdoor unit connection types.
Table 181: Outdoor Unit Piping Connections.
Indoor Unit Capacity Vapor Line Connection (in., OD) Liquid Line Connection (in., OD)
9,000 Btu/h
Ø3/8
Ø1/4
12,000 Btu/h
18,000 Btu/h
Ø1/2
24,000 Btu/h
36,000 Btu/h Ø5/8 Ø3/8
Table 182: Branch Distribution Unit Piping Connections.
Table 183: Indoor Unit Piping Connections.
Branch Distribution Unit PMBD3620 PMBD3630 PMBD3640 PMBD3641
Piping Connections to Outdoor Unit
Liquid (in., OD) x Qty. Ø3/8 x 1
Vapor (in., OD) x Qty. Ø3/4 x 1
Piping Connections to Indoor Units
Liquid (in., OD) x Qty. Ø1/4 x 2 Ø1/4 x 3 Ø1/4 x 4 Ø1/4 x 3, Ø3/8 x 1
Vapor (in., OD) x Qty. Ø3/8 x 2 Ø3/8 x 3 Ø3/8 x 4 Ø3/8 x 3, Ø5/8 x 1
Table 184: Connection Socket Dimensions.
Connection sockets (included as a factory-supplied accessory with the indoor units) may need to be used when piping the indoor units to the
branch distribution unit.
Indoor Unit Capacity
Vapor (in., OD) Liquid (in., OD)
A B A B
18,000 Btu/h
Ø3/8→Ø1/2 N/A
24,000 Btu/h
36,000 Btu/h Ø1/2→Ø5/8 Ø1/4→Ø3/8
Connection Socket
A
B
Figure 75: Branch Distribution Ports to Indoor Units.
ABC D
Figure 76: Connection Socket Diagram.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DESIGN & PRACTICES | 211
Refrigerant Piping Design and Best Practices