Wall Mounted Installation Manual

19
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MAX
MULTI
F
MULTI
F
Drilling the Piping Hole in the Wall
Follow all piping clearance recommendations.
1. Using a 2-9/16 to 2-5/8 inch hole core drill bit (depending on indoor model type), drill a
hole at either the right or left side of the wall mounting, pre-chosen following installation
guidelines and application needs.
The slant of the hole must be 3/16” to 5/16” from level with the slant being upward on
the indoor unit side and downward on the outdoor unit side.
2. Finish off the newly drilled hole as shown with bushing and sleeve covering to prevent
damage to the insulation and piping.
(3/16"~5/16")
Indoor
WALL
Outdoor
Bushing
Core Drill
Sleeve
Figure 8: Choice of Piping / Wiring Routes.
WARNING
Mounting hardware must be securely installed to prevent the chassis falling from its installation location. There is risk of injury or property
damage from falling equipment.
When choosing a location for the wall mount plate, be sure to take into consideration routing of wiring for power outlets within the wall. Touch-
ing wiring can cause serious bodily injury or death.
Installation work must be performed by trained personnel and in accordance with all local or other applicable codes. There is risk of injury to
personnel from incorrect installation.
Ensure the unit is properly installed. Incorrectly installed units can result in degraded performance or an inoperative unit / system.
Mounting hardware must be securely installed to prevent the chassis falling from its installation location. There is risk of property damage
from falling equipment.
Use a level indicator to ensure the installation plate and chassis are installed on a level plane.
If the unit is installed near a body of water, certain components are at risk of being corroded. Appropriate anti-corrosion methods must be
taken for the unit and all components.
Wall-mounted indoor units have several options on how the piping
and wiring can be routed (see figure at right). Whichever way the
piping and wiring are routed out of the indoor units, the mounting
wall on which the indoor unit is installed must be strong and solid
enough to protect it from vibration.
Mount the installation plate on the wall using the Type “A” screws.
If mounting the unit on concrete, consider using anchor bolts.
Always mount the installation plate horizontally. Measure the wall
and mark the center line using thread and a level.
Right Side
Piping
Piping / Drain Hose Holder
Left Side Piping
Rear
Piping
Figure 9: Drilling Piping Hole.
General Guidelines — HVT and HSV5 Wall-Mounted Indoor Units
INSTALLATION
&KRRVH3LSLQJDQG:LULQJ5RXWH'ULOOLQJ3LSLQJ+ROH