Wall Mounted Installation Manual

32
Multi F Standard Wall-Mounted Indoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MAX
MULTI
F
MULTI
F
Multi F MAX with LGRED Outdoor Unit System Piping Connections
Outdoor Unit Piping Connections LMU360HHV, LMU420HHV
Liquid Line Connection (in., OD) x Qty. Ø3/8 x 1
Vapor Line Connection (in., OD) x Qty. Ø3/4 x 1
Avoid Pipe Damage
When routing field-provided piping, avoid damaging the outdoor unit from excessive
vibration.
Properly insulate the liquid and gas lines separately up to the point of connection at
the unit frame.
See table below for Multi F MAX outdoor unit connection types.
Table 12: Multi F MAX with LGRED Outdoor Unit Piping Connections.
Torque
Wrench
Figure 41: Multi F MAX with LGRED Outdoor Unit
Refrigerant Pipe Connections.
Correctly route the piping so it does not make contact with mounting bolts. Allow room
IRU¿HOGLQVWDOODWLRQ
Multi F MAX with LGRED Outdoor Units
(36, 42 kBtu/h)
(Only for 18, 24 kBtu/h Indoor Units)
(Only for 36 kBtu/h Indoor Units
to Connect to “D ROOM”)
(Branch Distribution Unit: PMBD3640)
A ROOM
B ROOM
C ROOM
D ROOM
A ROOM
B ROOM
C ROOM
D ROOM
(Branch Distribution Unit: PMBD3641)
Branch Distribution to Indoor Unit Piping Connections
Install indoor unit liquid and vapor refrigerant pipes (and connection wiring) to the appropri-
ate branch distribution ports.
Clearly note on the indoor unit’s refrigerant piping (liquid, vapor) which branch distribution
port it is connected to (A, B, C, D).
Table 13: Branch Distribution Unit Piping Connections.
Branch
Distribution Unit
Refrigerant Connections
Pipe Size (in.)
Connectable Indoor Unit Capacity
(Btu/h)
Liquid Vapor
PMBD3620 Ø1/4 x 2 Ø3/8 x 2 7,000, 9,000, 12,000, 15,000, 18,000, 24,000
PMBD3630 Ø1/4 x 3 Ø3/8 x 3 7,000, 9,000, 12,000, 15,000, 18,000, 24,000
PMBD3640 Ø1/4 x 4 Ø3/8 x 4 7,000, 9,000, 12,000, 15,000, 18,000, 24,000
PMBD3641 Ø1/4 x 4
Ø3/8 x 3
7,000, 9,000, 12,000, 15,000, 18,000, 24,000
(A, B, C)
Ø1/2 x 1 36,000 (D)
Figure 42: Branch Distribution Ports to Indoor
Units -- Side View.
Figure 43: Branch Distribution Piping
Connections.
ABC D