Wall-Mounted Sensor Installation
Proper indoor unit operation depends on the location of the room sensor, if a room sensor is installed in addition to, or to use in place of a
controller. A good location will protect the sensor from direct sunlight and external local sources of water vapor, and air flow. If no mounting
height was specified by the building designer, place the handy box approximately four (4) to five (5) feet above the finished floor.
It could be necessary to use a handy box that is sized in metric units, depending on the sensor model. Check with your LG representative
to verify which size of handy box is needed for the sensor in question.
Communication cable from the indoor unit to the controller(s) is to be 22 AWG, 3-conductor, twisted, stranded, unshielded. Wiring must
comply with all applicable local and national codes. If using the LG Controller / Extension cable and the length needs to be further extend-
ed, the LG Extension Kit (sold separately) must be used. A maximum of four (4) kits (up to 165 feet) can be used.
Maintain at least the minimum distance required between the communications cable and power wiring. The minimum required space be-
tween the two depends on the voltage of the power wiring.
Do not route power wiring and communications cables in the same conduit. Routing power wiring and communications cables together
will cause communication errors and unit malfunction.
Do not cut the quick-connect plugs off or adjust the length of the cable. Keep the communications cable away from high voltage wires
and electromagnetic field (EMF) producing equipment. Performing these actions will cause communication errors and unit malfunction.
Wired Controller Installation
Wall indoor units can be used with various wired controllers (optional; sold separately). Wired controllers include a sensor to detect room
temperature. To maintain comfort levels in the conditioned space, the wired controller must be installed in a location away from direct
sunlight, high humidity, and where it could be directly exposed to cold air. Controller must be installed four (4) to five (5) feet above the floor
where its display can be read easily, in an area with good air circula-
tion, and where it can detect an average room temperature.
Do not install the remote controller where it can be impacted by the
following:
Drafts or dead spots behind doors and in corners
Hot or cold air from ducts
Radiant heat from sun or appliances
Concealed pipes and chimneys
Uncontrolled areas such as an outside wall behind the remote
controller
1. Pull communications cable between the controller handy box (if
used) and the indoor unit.
2. Store a minimal amount of cable in the handy box. Any additional
cable must be coiled and stored near the indoor unit control
panel.
3. If additional cable length is needed, communication cable from
the indoor unit to the remote controller(s) is to be 22 AWG,
3-conductor, twisted, stranded, unshielded. Wiring must comply with all applicable local and national codes. If using the LG Controller /
Extension cable and the length needs to be further extended, the LG Extension Kit (sold separately) must be used. A maximum of four (4)
kits (up to 165 feet) can be used.
4. If the cable between a zone controller and the indoor unit is too long,
do not cut. Coil any spare communications cable, tie-wrap it,
and leave it next to the indoor unit location.
4 to 5 feet
above the floor
NO
NO
NO
YES