Multi F PMBD3640 Submittal

Date:
JobName/Location:
PONo.:
Architect:
Engr:
GC:
Rep:
For:
File
A
pp
roval
Mech:
Resubmit
Other
Tag#:
(Company)
(ProjectManager)
PMBD3640
4PortBranchDistributionUnit(BDUnit)
Page1of2
SB_BDU_PMBD3640_10_16
Forcontinualproductdevelopment,LGreservestherighttochangespecificationswithoutnotice.
LGElectronicsU.S.A.,Inc.,EnglewoodCliffs,NJ.Allrightsreserved.“LGLife’sGood”isaregisteredtrademarkofLGCorp./www.lghvac.com
Performance:
Electrical:
PowerSupply(V¹/Hz/Ø)
208230/60/1
PowerInput(W)
32
RatedAmps(A)
0.16
Piping:
LiquidLine(in,OD)
3/8
VaporLine(in,OD)
3/4
PipingConnectiontoOutdoorUnit:
PipingConnectiontoIndoorUnit:
LiquidLine(in,OD)
1/4(Qty4)
VaporLine(in,OD)
3/8(Qty4)
OperatingRange:
NetWeight(lbs)
16
ShippingWeight(lbs)
18
StandardFeatures:
•Distributesrefrigeranttoindoorunits
•Internalcomponentsareinsulated
•Flarejointsprovidedforeasyinstallaon
•Compactdesign
Notes:
1.Acceptableoperangvoltage:187V253V.
2.Allpower/communicaoncabletobeminimum16AWGfromtheoutdoo runittotheBD
unitand18AWGfromtheBDunittotheindoorunit.
3.Allpower/communicaoncabletobe4conductor,stranded,shieldedandmustcomply
withapplicablelocalandnationalcode.
4.Pipinglengths:
•Maximumheightdierencebetween BDunitandindoorun its‐32.8
•Maximumheightdierencebetween BDunitandBDunit‐49.2.
•MaximumpipinglengthbetweenBDunitandindoorunits‐49.2
5.TheBDunitshouldbeinstalledinsideofabuilding.
6.MustfollowinstallaoninstruconsintheapplicableLGinstallaonmanual.
7.Powerwiringcablesizemustcomplywiththeapplicablelocalandnaonalcode.
MaxNominalPortCapacityBtu/h(eachport)
24,000
MaxNominalUnitCapacityBtu/h(sumofports)
73,000
UnitData:
OperatingRange(°FDB)
0150

Summary of content (2 pages)