Multi F Four-Way Ceiling Cassette Service Manual

- 51 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 5. Trouble Shooting
Check the Volt.
Indoor Unit
V
12Vdc
12V S GND
Check the Volt.
Wired R/C
V
12Vdc
12V S GND
CN-REMO
03
Communication
Wired R/C
• Open / Short
• Wrong connection
• Connection of wire
• Main PCB Volt. DC12V
• Noise interference
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Check the wire connection. (Open / Short) Repair the connection
2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation