Multi F Four-Way Ceiling Cassette Service Manual

Part 5. Trouble Shooting
- 88 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
29
Inverter compressor over
current
Inverter compressor input
current is over 30A
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref. over-
charge)
2. Compressor damage(Insulation damage/Motor
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
Display
code
Title Cause of error Check point & Normal condition
Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
Reassemble or manage if abnormality found
Yes
Is input voltage normal?
No
Check
L~N phase is 230V±15%
Check connection condition and wiring if power is
abnormal
Yes
Is inverter PCB assembly
normal?
No
Check inverter PCB assembly IPM normality
Replace inverter PCB assembly
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
1. Check resistance between each terminal of compressor
(0.438~0.628±7%)
2. Check insulation resistance between compressor
terminal and pipe (over 2M
Ω)
Replace compressor if abnormality found
Is compressor
Wire connection
condition normal?
No
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
Reassemble if abnormality found
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.