LGRED Installation Manual

21
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
WITH
PLACEMENT CONSIDERATIONS
Minimum 12
Air inlet grille
Blown
air
Strong
wind
Strong
wind
Minimum 12
Minimum 24
Sunroof
Fence or
obstacles
Minimum 12
Air inlet grille
Blown
air
Strong
wind
Strong
wind
Minimum 20
Fence or
obstacles
Unit: Inch
Minimum 12
Ensure that the space at the back of the outdoor unit is a minimum of 12 inches, and
include a minimum of 24 inches at the right side of the unit for service.
If the outdoor unit discharge side faces a wall, include a minimum of 20 inches between
the outdoor unit and the wall. Install the outdoor unit so that the discharge port is set at a
right angle to the wind direction.
Multi F MAX with LGRED Outdoor Unit (36,000, 42,000, 48,000 Btu/h Capacity) Service Access and Allowable Clearances
When installing the outdoor unit, consider service, inlet, and outlet, and minimum allowable space requirements as illustrated in the following
diagrams.
Clearance Requirements when Different Obstacles are Present (Unit: Inch).
Selecting the Best Location for the Outdoor Unit
Minimum 12"
Minimum 40"
Obstacles above and on
the air intake side.
Maximum 20"
Minimum 12"
Minimum 12"
Minimum 12
"
Minimum 24
"
Obstacle on the suction side
only.
Obstacles on the suction side
and on both left and right sides.
Minimum 12"
Maximum 20
"
Minimum 12"
Minimum 40"
Minimum 24"
Obstacles above, on the air intake
side, and on both left and right sides.
Minimum 20"
Obstacle just on the air
discharge side.