ELECTRICAL
LG Terminal Connections
LG uses a “JIS” type of screw for all terminals; use a JIS screwdriver to tighten and
loosen these screws and avoid damaging the terminal. Do not over tighten the
connections — over tightening will damage the terminals — but firmly and securely at-
tach the wiring in a way to prevent external forces from being imparted to the terminal
block.
7KHWHUPLQDOVODEHOHG³*1'´DUH127JURXQGWHUPLQDOV7KHWHUPLQDOVODEHOHG
ARE ground terminals.
3RODULW\PDWWHUV$OZD\VFRQQHFW³$´WR³$´DQG³%´WR³%´
Always create a wiring diagram that contains the exact sequence in which all the indoor units and branch distribution units (Multi F MAX
systems only) are wired in relation to the outdoor unit.
Do not include splices or wire nuts in the communication cable.
Figure 73: JIS Screws.
Always have a trained service provider properly ground the outdoor unit. If the outdoor unit is not properly grounded, there is a risk of
electric shock, physical injury, or death.
Provide a circuit breaker between the power source and the outdoor unit. Failure to do so will cause bodily injury or death.
Multi F and Multi F MAX systems operate at 1Ø, 208-230V, 60Hz, and power is wired
to the outdoor unit only. The outdoor unit will supply power to the indoor units and the
branch distribution units (Multi F MAX systems only) through the communication / con-
nection (power) cable.
Power supply to the outdoor unit must be selected based on NEC and local codes. Maxi-
mum allowable voltage fluctuation ±10% or nameplate rated value.
Power wiring to the outdoor unit(s) must be solid or stranded, and must comply with all
local and national electrical codes.
Properly ground the outdoor unit and indoor unit per NEC and local codes.
Ground wire must be longer than the common power / communication wires.
Connect the wiring firmly so the wires cannot be easily pulled out.
Refer to the inside of the chassis cover or control cover for circuit and terminal block
diagrams.
Always match color codes of each wire and follow wiring diagram.
Do not install power wiring to the outdoor unit and the communication / connection (power) cable to the indoor unit in the same conduit.
Use separate conduits.
3RZHU6XSSO\3RZHU:LULQJ6SHFLILFDWLRQV
Air
Conditioner
Main Power Source
Circuit Breaker
Use a circuit breaker
or time delay fuse
Figure 74: Circuit BreakerTable 32: Circuit Breaker / Fuse Size.
7/16" ± 1/8"
13/16
"
GN/YL
Power Wiring, Ground
to Outdoor Unit
Figure 75: Multi F / Multi F MAX Outdoor Unit
Power Wiring.
&RQQHFWLRQVDQG6SHFL¿FDWLRQV
Outdoor Unit Model Power Source
Fuse or Breaker
Capacity
LMU18CHV, LMU24CHV 1Ø, 208-230V 20A
LMU30CHV, LMU36CHV 1Ø, 208-230V 25A
LMU480HV, LMU540HV 1Ø,208-230V 40A
LMU600HV 1Ø, 208-230V 45A