External Static Pressure
FOUR-WAY VAHU INDOOR UNITS
Heater Capacity Static Pressure Drop (in. wg)
0 0
3, 5 -0.01
8, 10 -0.02
Table 91: Electric Heater Static Pressure Drop Factors.
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5)
High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0)
High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0)
High (990) -0.04
Middle(880) -0.04
Low (800) -0.04
Table 92: Down Flow (optional) Static Pressure Drop Factors.
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5)
High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0)
High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0)
High (990) -0.04
Middle(880) -0.04
Low (800) -0.04
Table 93: Down Flow Air Filter Static Pressure Drop Factors
Heater Capacity (kW) Static Pressure Drop (in. wg)
0 0
3, 5 -0.01
8, 10 -0.01
Table 94: Down Flow Internal Electric Heater Static Pressure Drop.