LMCN078HV Engineering Manual

EQUIPMENT SELECTION PROCEDURE
Table 104: Allowable Indoor Unit to Multi F / Multi F MAX with LGRED Outdoor Unit Connections.
Branch Distribution Unit (PMBD3620)
+
24 x 1.2 24 x 1.2 + Total Capacity Index = = 57.6 < 73
Branch Distribution Unit (PMBD3641)
First Indoor Unit:
LMCN125HV
+ + Outdoor Unit: LMU540HV
12 9 36 x 1.3 + + Total Capacity Index = = 67.8 < 73
Acceptable
Combination
Second Indoor Unit:
LSN090HSV4
Third Indoor Unit:
LVN361HV4
Outdoor Unit: LMU540HV
First Indoor Unit:
LVN241HV4
Second Indoor Unit:
LVN241HV4
Acceptable
Combination
Example 1
Example 2
Multiplier Examples
Indoor units Outdoor units
Model Type
Indoor Unit Nominal
Capacity (Btu/h)
LMU18CHV LMU24CHV LMU30CHV LMU36CHV LMU480HV LMU540HV LMU600HV
Maximum No. of Connectable Indoor Units
2 3 4 4 8 8 8
ART COOL Mirror
9,000 O O O O O O O
12,000 O O O O O O O
18,000 - O O O O O O
ART COOL Gallery
9,000 O O O O O O O
12,000 O O O O O O O
Standard Wall Mounted
7,000 O O O O O O O
9,000 O O O O O O O
12,000 O O O O O O O
15,000 O O O O O O O
18,000 - O O O O O O
24,000 - O O O O O O
Low Wall Console
9,000 O O O O O O O
12,000 O O O O O O O
15,000 O O O O O O O
Ceiling Concealed Duct-
Low Static
9,000 O O O O O O O
12,000 O O O O O O O
18,000 - O O O O O O
Ceiling Concealed Duct-
High Static
24,000 - - O O O O O
36,000 - - - - O O O
Four-Way Ceiling Cassette
7,000 O O O O O O O
9,000 O O O O O O O
12,000 O O O O O O O
18,000 - O O O O O O
Vertical-Horizontal Air Handler
18,000 - O O O O O O
24,000 - - O O O O O
36,000 - - - - O O O
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
APPLICATION GUIDELINES | 187
Application Guidelines
MULTI
F
MAX
MULTI
F