Table 43: Multi F Ceiling-Concealed Duct (Low Static) Indoor Units Heating Capacity Table.
DUCT (LOW STATIC) INDOOR UNITS
Heating Capacity Table
Model No. /
Nominal Capacity of
Indoor Unit
(Btu/h)
Outdoor Air Temp. Indoor Air Temp. °F DB
°F DB °F WB
61 64 68 70 72 75
TC TC TC TC TC TC
LDN097HV4
9,000
0 -0.4 5.35 5.28 5.23 5.20 5.12 4.90
5 4.5 6.03 5.95 5.90 5.88 5.80 5.58
10 9 6.71 6.63 6.58 6.56 6.48 6.26
17 15 7.61 7.54 7.49 7.46 7.39 7.14
20 19 7.95 7.88 7.83 7.80 7.72 7.46
25 23 8.52 8.44 8.39 8.37 8.29 7.99
30 28 9.01 8.93 8.88 8.86 8.78 8.52
35 32 9.50 9.42 9.37 9.34 9.27 9.04
40 36 9.94 9.86 9.81 9.78 9.71 9.48
45 41 10.37 10.30 10.25 10.22 10.15 9.92
47 43 10.55 10.48 10.43 10.40 10.32 10.10
50 46 10.72 10.64 10.59 10.57 10.49 10.24
55 51 11.00 10.93 10.88 10.85 10.78 10.48
60 56 11.00 10.93 10.88 10.85 10.78 10.52
63 59 11.00 10.93 10.88 10.85 10.78 10.55
68 64 11.00 10.93 10.88 10.85 10.78 10.60
LDN127HV4
12,000
0 -0.4 7.10 7.00 6.93 6.90 6.80 6.50
5 4.5 8.00 7.90 7.83 7.80 7.70 7.40
10 9 8.90 8.80 8.73 8.70 8.60 8.30
17 15 10.10 10.00 9.93 9.90 9.80 9.48
20 19 10.55 10.45 10.38 10.35 10.25 9.90
25 23 11.30 11.20 11.13 11.10 11.00 10.60
30 28 11.95 11.85 11.78 11.75 11.65 11.30
35 32 12.60 12.50 12.43 12.40 12.30 12.00
40 36 13.18 13.08 13.02 12.98 12.88 12.58
45 41 13.77 13.67 13.60 13.57 13.47 13.17
47 43 14.00 13.90 13.83 13.80 13.70 13.40
50 46 14.23 14.13 14.06 14.03 13.93 13.59
55 51 14.60 14.50 14.43 14.40 14.30 13.90
60 56 14.60 14.50 14.43 14.40 14.30 13.96
63 59 14.60 14.50 14.43 14.40 14.30 14.00
68 64 14.60 14.50 14.43 14.40 14.30 14.06
LDN187HV4
18,000
0 -0.4 10.70 10.55 10.45 10.40 10.25 9.80
5 4.5 12.06 11.91 11.81 11.76 11.61 11.15
10 9 13.41 13.26 13.16 13.11 12.96 12.51
17 15 15.22 15.07 14.97 14.92 14.77 14.29
20 19 15.90 15.75 15.65 15.60 15.45 14.92
25 23 17.03 16.88 16.78 16.73 16.58 15.98
30 28 18.01 17.86 17.76 17.71 17.56 17.03
35 32 18.99 18.84 18.74 18.69 18.54 18.09
40 36 19.87 19.72 19.62 19.57 19.42 18.97
45 41 20.75 20.60 20.50 20.45 20.30 19.85
47 43 21.10 20.95 20.85 20.80 20.65 20.20
50 46 21.44 21.29 21.19 21.14 20.99 20.48
55 51 22.01 21.86 21.75 21.70 21.55 20.95
60 56 22.01 21.86 21.75 21.70 21.55 21.04
63 59 22.01 21.86 21.75 21.70 21.55 21.10
68 64 22.01 21.86 21.75 21.70 21.55 21.20
TC = Total Capacity (kBtu/h).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor units. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).