Multi F MAX LMU481HV Submittal

Refrigerant Charge (lbs.)
Liquid Line Connecon (in., O.D.)
Vapor Line Connecon (in., O.D.)
Maximum Total Piping² (.)
Min. / Max. ODU to IDU Piping
3
(.)
Piping Length
4
(no add’l refrigerant, .)
Maximum Elevaon between ODU and IDU (.)
Maximum Elevaon between IDU and IDU (.)
For: File Resubmit
Approval Other
Job Name/Locaon:
Date:
PO No.:
Architect:
GC:
Engr:
Mech:
Rep:
(Company) (Project Manager)
Tag No:
Features:
For a complete list of available accessories, contact your LG representave.
For connual product development, LG reserves the right to change specicaons without noce.
© LG Electronics U.S.A., Inc., Englewood Clis, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Oponal Accessories:
Performance:
Cooling Capacity (Min.‐Rated‐Max., Btu/h)
Heang Capacity (Min.‐Rated‐Max., Btu/h)
Max. Heang Capacity at 17°F (Btu/h)
Max. Heang Capacity at 5°F (Btu/h)
Max. Heang Capacity at ‐4°F (Btu/h)
Cooling COP @95°F (Rated)
Heang COP @47°F (Rated)
Electrical:
Power Supply (V/Hz/Ø)
1
MOP (A)
MCA (A)
Cooling Rated Amps (A)
Heang Rated Amps (A)
Compressor (A)
Fan Motor (A)
Locked Rotor Amps (A)
208‐230V, 60, 1
40
32.7
22.0
1.6 x 2
22
Page 1 of 3
Cooling (°F DB)¹
5
Heang (°F WB)
14 to 118
‐4 to +64
Operang Range:
Unit Data:
Type
Quanty
Oil / Type
R1 Scroll
1
FVC68D
Compressor:
PI‐485 ‐ PMNFP14A1
AC Smart 5 ‐ PACS5A000
ACP 5 ‐ PACP5A000
MulSITE Comm. Mgr. ‐ PBACNBTR0A
Power Distribuon Indicator (PDI)
Premium ‐ PQNUD1S41
Mobile LGMV ‐ PLGMVW100
Low Ambient Wind Bae (Cooling
Operaon Down to ‐4°F) ‐ ZLABGP04A x2
Drain Pan Heater ‐ PQSH1200
Piping:
R1 Scroll (Variable
Speed) Compressor
Auto operaon
Auto restart
Self diagnosis
Defrost / Deicing
Low ambient cooling
down to 14°F
So start
Restart delay (three
[3] minutes)
Cooling Nominal Test Condions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Heang Nominal Test Condions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
Notes:
1. Acceptable operang voltage: 187V ‐ 253V.
2. Piping lengths are equivalent.
3. 180.4 . of Main Piping + 49.2 . of Branch Piping.
4. 49.2 . of Main Piping + 131.2 of Branch Piping.
5. At least one branch distribuon (BD) unit is required for system operaon; a
maximum of two can be installed per ODU with the use of a Y‐branch accessory
(PMBL5620).
6. Sound pressure levels are tested in an anechoic chamber under ISO Standard
3745.
7. All power / communicaon cable to be minimum 14 AWG from the ODU to the
BD unit, and 14 AWG from the BD unit to the IDU.
8. All power / communicaon cable to be 4‐conductor, stranded, shielded or un
shielded, and must comply with applicable local and naonal codes. If shielded,
the wire must be grounded to the chassis at the ODU only.
9. Power wiring size must comply with the applicable local and naonal codes.
10. See the Engineering Manual Capacity Tables for ODU sensible and latent capacies.
11. See the Engineering Manual Combinaon Tables for allocaon of ODU rated
capacity to each connected IDU when all are calling for full capacity. Allocaon
percentages should be applied to ODU capacity at design condions.
12. This data is rated 0 . above sea level, with 115 . of refrigerant line, and 0 .
level dierence between ODU and IDUs. All capacies are net with a combinaon
rao between 95 ‐ 105%.
13. Must follow installaon instrucons in the applicable LG installaon manual.
14. See the Engineering Manual Capacity Tables for ODU capacity at design condi
ons.
15. Installaon of an oponal Low Ambient Wind Bae Kit will allow operaon
down to ‐4°F in cooling mode.
Refrigerant Type
Refrigerant Control
Sound Pressure (Cool / Heat) ±1 dB(A)
6
Net / Shipping Weight (lbs.)
Heat Exchanger Coang
Minimum No. of Indoor Units
Maximum No. of Indoor Units
Type
Quanty
Motor / Drive
Max. Airow Rate (CFM)
Propeller
2
Brushless Digitally Controlled/Direct
Fan:
Ø3/8 x 1
Ø3/4 x 1
475.7
32.8 / 229.6
180.4
98.4
49.2
MOP ‐ Maximum Overcurrent Protecon MCA ‐ Minimum Circuit Ampacity
ODU = Outdoor Unit IDU = Indoor Unit
R410A
EEV
Gold Fin
2
Required
5
Accessories:
2 Port BD Unit ‐ PMBD3620
3 Port BD Unit ‐ PMBD3630
4 Port BD Unit ‐ PMBD3640
4 Port BD Unit ‐ PMBD3641
12,420~54,000~59,000
29.2
47,690
53 / 55
192 / 216
9.26
3.75
SB_MultiF_MAX_LMU481HV_2021_09_08_125816
35,070
29.2
1,942 x 2
LMU481HV
4.0 Ton Heat Pump
10,800~48,000~58,000
3.50
40,190
Multi F MAX Outdoor Unit

Summary of content (3 pages)