Multi F Installation Manual

9
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
SPECIFICATIONS
Multi F MAX Outdoor Units
Table 2: Multi F MAX Outdoor Unit General Data.
Model Number LMU480HV LMU540HV LMU600HV
Cooling Capacity (Btu/h) (Minimum ~ Rated ~ Maximum)
1
14,400~48,000~58,000 14,400~52,500~63,200 15,600~60,000~68,000
Heating Capacity (Btu/h)
(Minimum ~ Rated ~ Maximum)
1
15,840~54,000~61,000 16,272~58,000~64,000 17,940~64,000~70,000
Operating Range
Cooling (°F DB) 14
7
- 118 14
7
- 118 14
7
- 118
Heating (°F WB) -4 - 64 -4 - 64 -4 - 64
Compressor
Inverter Quantity Twin Rotary x 1 Twin Rotary x 1 Twin Rotary x 1
Oil Type FVC68D FVC68D FVC68D
Fan (Side Discharge)
Type Propeller Propeller Propeller
Motor Output (W) x Qty. 124.2 x 2 124.2 x 2 124.2 x 2
Motor/Drive Brushless Digitally Controlled/Direct
Maximum Air Volume (CFM) 2,119 x 2 2,119 x 2 2,119 x 2
Unit Data
Refrigerant Type R410A R410A R410A
Refrigerant Control/Location EEV / Outdoor Unit, Branch Distribution Unit
Min. Number Indoor Units/System
2
222
Max. Number Indoor Units/System
2
888
Maximum Allowable Total Indoor Unit Connected Capacity (Btu/h) 65,000 73,000 81,000
Sound Pressure ±3 dB(A)
3
(Cooling / Heating) 54 / 56 54 / 56 56 / 58
Net Unit Weight (lbs.) 214 214 223
Shipping Weight (lbs.) 236 236 249
Power/Communications Wiring Between ODU and BD Unit
(No. X AWG)
4,5
4C X 16 4C X 16 4C x 16
Heat Exchanger
Material and Fin Coating Copper Tube / Aluminum Fin and GoldFin™/Hydrophilic
Rows/Columns/Fins per inch x Qty. (2 x 32 x 14) x 2 (2 x 32 x 14) x 2 (3 x 32 x 14) x 2
Piping
Liquid Line Connection (in., OD) x Qty. 3/8 x 1 3/8 x 1 3/8 x 1
Vapor Line Connection (in., OD) x Qty. 3/4 x 1 3/4 x 1 3/4 x 1
Factory Charge lbs. of R410A 9.7 9.7 12.3
Piping Lengths
Maximum Total System Piping (ft.)
6
475.7 475.7 475.7
Maximum Main Pipe Length (Outdoor Unit to BD Unit [ft.]) 180.4 180.4 180.4
Total Branch Piping (BD Units to all Indoor Units [ft.]) 295.3 295.3 295.3
Maximum Branch Pipe Length (Length between each
BDU and IDU [ft.])
49.2 49.2 49.2
Maximum Outdoor Unit to Indoor Unit Pipe Length (ft.) 229.6 229.6 229.6
Max. Main Piping Length (No Additional Refrigerant (ft.) 16 16 16
Max. Branch Piping Length (No Additional Refrigerant (ft.) 131 131 147.6
Maximum Elevation between Outdoor Unit and Indoor Unit (ft.) 98.4 98.4 98.4
Maximum Elevation between Indoor Unit and Indoor Unit (ft.) 49.2 49.2 49.2
Maximum Elevation between BD Unit and Indoor Unit (ft.) 32.8 32.8 32.8
Maximum Elevation between BD Unit and BD Unit (ft.) 49.2 49.2 49.2
1
Rated capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level with a 0
ft. level difference between outdoor and indoor units. All capacities are net with a combination
ratio between 95 – 105%.
Rated cooling capacity obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF
wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
At least one Branch Distribution Unit is required for system operation; a maximum of two can
be installed per outdoor unit with use of Y-branch accessory (PMBL5620). At least two indoor
units should be connected. For allocated capacity information, see the combination tables in
the “Multi F / Multi F MAX Combination Data Manual” on www.lg-dfs.com. For performance
data, see “Multi F / Multi F MAX Performance Data Manual” on www.lg-dfs.com.
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
These values can increase due to ambient conditions during operation.
4
3RZHUZLULQJWRWKHRXWGRRUXQLWLV¿HOGVXSSOLHGVROLGRUVWUDQGHGDQGPXVWFRPSO\ZLWK
the applicable local and national codes. For detailed information, please refer to electrical
characteristics on page 11.
5
All power wiring / communication cable to be minimum 16 AWG from the outdoor unit to
the BD unit (Multi F MAX systems only), and 18 AWG from the BD unit to the indoor unit,
stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the
outdoor unit only), and must comply with applicable local and national codes. For detailed
electrical information, please refer to electric characteristics on page 11.
6
Piping lengths are equivalent.
7
,QVWDOODWLRQRIDQRSWLRQDO/RZ$PELHQW:LQG%DIÀH.LWZLOODOORZRSHUDWLRQGRZQWR)LQ
cooling mode.