Engineering Manual
Table Of Contents
- Convergence of Technology, Innovation, Flexibility, & Style
 - Unit Nomenclature
 - Outdoor Unit Overview
 - Indoor Unit Overview
 - Controls and Options Overview
 - Art Cool Mirror Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - Acoustic Data
 - Air Velocity and Temperature Distribution
 - Refrigerant Flow Diagram
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Art Cool Gallery Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - Acoustic Data
 - Air Velocity and Temperature Distribution
 - Refrigerant Flow Diagram
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Standard Wall-Mounted Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - Acoustic Data
 - Air Velocity and Temperature Distribution
 - Refrigerant Flow Diagram
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Duct (Low Static) Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - External Static Pressure
 - Acoustic Data
 - Refrigerant Flow Diagrams
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Duct (High Static) Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - External Static Pressure / Acoustic Data
 - Refrigerant Flow Diagrams
 - Wiring Diagrams
 - Factory Supplied Parts and Materials / Installation
 - Installation and Best Layout Practices
 - Four-Way Ceiling Cassette Indoor Units
 - General Data / Specifications
 - Dimensions
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - Acoustic Data
 - Air Velocity and Temperature Distribution
 - Refrigerant Flow Diagram
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Vertical-Horizontal Indoor Units
 - General Data / Specifications
 - Dimensions
 - Cooling Capacity Table
 - Heating Capacity Table
 - External Static Pressure
 - Acoustic Data
 - Refrigerant Flow Diagram
 - Wiring Diagram
 - Factory Supplied Parts and Materials
 - Installation and Best Layout Practices
 - Equipment Selection Procedure
 - Building Ventilation Design Guide
 - Placement Considerations
 - Refrigerant Piping Design
 - Design Guideline Summary
 - Creating a Balanced System / Manual Layout Procedure
 - LG Engineered Multi F MAX Y-Branch Kit
 - Refrigerant Charge
 - Installation & Layout Best Practices
 - Refrigerant Piping System Layout
 - Piping Insulation
 - Condensate Drain Piping
 - Y-Branch Kit
 - Wiring Connections
 - Power Wiring (208-230V) and Communications Cable Details
 - Indoor Unit Group Control
 - Acronyms
 
DUCT (LOW STATIC) INDOOR UNITS
• Measurements taken with no attenuation and units operating at full 
load normal operating condition.
• Sound level will vary depending on a range of factors such as 
construction (acoustic absorption coefficient) of particular area in 
which the equipment is installed.
• Sound power levels are measured in dB(A)±3.
• Tested in anechoic chamber per ISO Standard 3745.
Model No.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
High Fan Speed
Medium Fan 
Speed
Low Fan Speed
LMDN096HV 30 26 23
LMDN126HV 31 28 27
LMDN186HV 36 34 31
Figure 124: Sound Pressure Level Measurement Location.
Table 46:Sound Pressure Levels (dB[A]).
Figure 125: Sound Pressure Level Diagrams.
Acoustic Data
4.9 ft.
Ceiling
6.6 ft.
Microphone
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10 
20 
30 
40 
50 
60 
70 
80 
63  125  250  500  1000  2000  4000  8000 
NC-15 
NC-20 
NC-25 
NC-30 
NC-35 
NC-40 
NC-45 
NC-50 
NC-55 
NC-60 
NC-65 
Approximate
Hearing
Threshold 
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10 
20 
30 
40 
50 
60 
70 
80 
63  125  250  500  1000  2000  4000  8000 
NC-15 
NC-20 
NC-25 
NC-30 
NC-35 
NC-40 
NC-45 
NC-50 
NC-55 
NC-60 
NC-65 
Approximate
Hearing
Threshold 
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10 
20 
30 
40 
50 
60 
70 
80 
63  125  250  500  1000  2000  4000  8000 
NC-15 
NC-20 
NC-25 
NC-30 
NC-35 
NC-40 
NC-45 
NC-50 
NC-55 
NC-60 
NC-65 
Approximat e
Hearing
Threshold 
LMDN096HV LMDN126HV LMDN186HV
DUCT (LOW STATIC) | 97
Ceiling-Concealed Duct (Low Static)
Due to our policy of continuous product innovation, some specications may change without notication.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI 
F
MAX
MULTI 
F










