LMU540HV Installation Guide

20
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
GENERAL INSTALLATION GUIDELINES
Selecting the Best Location for the Branch Distribution (BD) Unit
Branch Distribution (BD) units are used only with Multi F MAX systems to distribute the refrigerant from the outdoor unit to up to eight indoor
units. Select location indoors that will meet the following conditions:
Within allowable parameters for proper connection to the Multi F MAX outdoor unit and indoor unit(s); refrigerant piping and wire lengths
must not exceed amounts specified by LG Electronics, U.S.A., Inc.
Condensate drain piping is not required.
Ensure there is enough space in the installation area for service and inspection purposes (23-5/8 inch square opening).
Install the refrigerant piping and electrical wiring system in an easily accessible location.
Level where there is enough strength to bear the weight of the BD unit.
Interior installation is highly recommended.
$OORZDEOHRSHUDWLQJWHPSHUDWXUHUDQJHa)$OORZDEOHPD[LPXPRSHUDWLQJKXPLGLW\UDQJH
Unit can be installed no more than ±5 degrees of level.
Do not install the BD unit in a location where it would be subjected to strong radiation heat from heat sources.
Avoid an installation environment where the BD unit would be exposed to heat, water, steam, oil splattering, spray or other factors that may
damage the PCB.
Install the unit in a location where any sound it generates will not disturb occupants in the surrounding rooms.
No obstacles to air circulation around the unit; keep proper distances from ceilings, doorways, floor, walls, etc.
Where high-frequency electrical noise / electromagnetic waves will not affect operation. Maintain proper distances between the BD unit(s)
and electric wires, audio and visual appliances, breaker / circuit panels, etc.
Location for Multi F MAX Branch Distribution Units
PCB
1-31/321-3/16
4-3/8
Service Direction
Piping to
Indoor Units
Service Direction