Installation and Best Layout Practices
DUCT (HIGH STATIC) INDOOR UNITS
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms will be exposed to unconditioned air (room will be above or next to an
XQKHDWHGJDUDJHRUVWRUHURRP7RFRXQWHUPHDVXUH
Verify that carpet is or will be installed (carpet will increase the temperature by three degrees).
Add insulation between the floor joists.
Install radiant heat or another type of heating system to the floor.
Installing in an Area with High Humidity Levels
,IWKHHQYLURQPHQWLVSURQHWRKXPLGLW\OHYHOVRIRUPRUHQHDUWKHRFHDQODNHVHWFRUZKHUHVWHDPFRXOGFROOHFWLQWKHSOHQXP
Install additional insulation to the indoor unit (glass wool insulation >13/32 inches thick).
Install additional insulation to the refrigerant piping (insulation >13/16 inches thick).
Seal all gaps between the indoor unit and the ceiling tiles (make the area air tight) so that humidity does not transfer from the plenum to the
conditioned space. Also, add a ceiling grille for ventilation.
)LJXUH Access Panel and General Service Space Required
Dimensions.
)LJXUH Indoor Unit Bolt Locations.
Drain hole
A
B
CD
G
H
I
EF
23-5/8 inches x 23-5/8 inches
23-5/8
inches
39-3/8
inches
H = ≥25/32 inches
23-5/8
inches
Model / Capacity
(Btu/h)
Dimensions (inches)
ABCDEFGH I
LMHN240HV / 24,000
48-17/32 46-17/32 13-31/32 1-25/32 17-23/32 1-7/32 3-5/8 32-19/32 7-11/32
LMHN360HV / 36,000
7DEOHIndoor Unit Bolt Location Dimensions.
,QGRRUXQLWV,'8VPXVWQRWEHSODFHGLQDQHQYLURQPHQWZKHUHWKH,'8VZLOOEHH[SRVHGWRKDUPIXOYRODWLOHRUJDQLFFRPSRXQGV92&V
RULQHQYLURQPHQWVZKHUHWKHUHLVLPSURSHUDLUPDNHXSRUVXSSO\RULQDGHTXDWHYHQWLODWLRQ,IWKHUHDUHFRQFHUQVDERXW92&VLQWKHHQYL
URQPHQWZKHUHWKH,'8VDUHLQVWDOOHGSURSHUDLUPDNHXSRUVXSSO\DQGRUDGHTXDWHYHQWLODWLRQPXVWEHSURYLGHG$GGLWLRQDOO\LQEXLOGLQJV
ZKHUH,'8VZLOOEHH[SRVHGWR92&VFRQVLGHUDWKLUGSDUW\IDFWRU\DSSOLHGHSR[\FRDWLQJWRWKHIDQFRLOVIRUHDFK,'8ZKHUHWKHHQWLUHFRLO
is dipped, not sprayed.
,IWKHXQLWLVLQVWDOOHGQHDUDERG\RIZDWHUWKHLQVWDOODWLRQSDUWVDUHDWULVNRIFRUURGLQJ$SSURSULDWHDQWLFRUURVLRQPHWKRGVPXVWEHWDNHQIRU
the unit and all installation parts.
DUCT (HIGH STATIC) | 105