Multi F Engineering Manual

MULTI
F
MAX
MULTI
F
1. Select and mark the area for the suspension or console bolts (use
embedded inserts or anchor bolts in new buildings, and hole-in-
anchors in older buildings).
2. Drill the holes.
3. Add the set-anchor and the plate washer to the bolts (bolts must
be at least 13/32 inches in diameter), and then insert the bolts
into the installation area.
4. Add the plate washer, spring washer, and nut to secure the bolts
into the installation area.
5. Position the indoor unit installation plates onto the bolts. Secure
using nuts, plate washers, and spring washers. Adjust for level as
necessary.
Unit must be installed correctly. Tighten the nuts and bolts to prevent the unit from falling and
causing severe injury or death.
)LJXUH Preparing the Installation Area.
Install a canvas duct to the air outlet and air inlet so that vibration from the indoor unit does not
FDUU\WRWKHGXFWRUFHLOLQJ$OVRDGGLQVXODWLRQWRWKHLQWHULRURIWKHGXFWDQGDSSO\DQWLYLEUDWLRQ
to the suspension bolts.
Preparing the Installation Area and Hanging the Indoor Unit Frame
)LJXUH Suspension Bolt Options.
)LJXUH Hanging the Indoor Unit.
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Field-
supplied)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
X 4
(Field-
supplied)
'RQRWDSSO\IRUFHRUWZLVWWKHGUDLQKRVHLWZLOOOHDN
1/50~1/100 slope
Hanger distance
3.3~49.2 feet
Hanger Bracket
Maximum
27-9/16 inches
Flexible drain hose
Insulation
Metal
clamp
Maximum
11-13/16 inches
Installing the Drain System
Drain piping must have downward gradient of at least 1/50 to 1/100; to prevent reverse flow, slope must
not be straight up and down.
Do not damage the drain port on the indoor unit when connecting the field-supplied drain piping.
'UDLQSLSLQJVSHFLILFDWLRQV
,QGRRU8QLW'UDLQ&RQQHFWLRQLQFKRXWVLGHGLDPHWHU
)LHOG6XSSOLHG'UDLQ3LSLQJ3RO\YLQ\OFKORULGHSLSLQJZLWKLQFKLQVLGHGLDPHWHUDQGSLSHILWWLQJV
Drain Port
Maintenance
Drain Pipe Support
Indoor unit
1/50~1/100mm
Maximum
27-9/16 inches
)LJXUHIndoor Unit Drain Piping.
)LJXUHDrain Piping Installation Dimensions.
Installation and Best Layout Practices
DUCT (HIGH STATIC) INDOOR UNITS
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
106 | DUCT (HIGH STATIC)
Multi F and Multi F MAX Indoor Unit Engineering Manual