Installation and Best Layout Practices
DUCT (HIGH STATIC) INDOOR UNITS
Using a Conduit
1. Remove the rubber stopper on the indoor unit. Pass the power wiring / communica-
tions cable through the conduit, the conduit mounting plate, and to / through the
control panel of the indoor unit.
2. Connect the power wiring / communications cable to the indoor unit terminal block.
3. Screw the conduit mounting plate to the indoor unit.
4. Tighten the conduit and the conduit mounting plate together.
If the distance between the outdoor unit and indoor unit is greater than 131 feet, connect
WKHSRZHUZLULQJDQGFRPPXQLFDWLRQVFDEOHVHSDUDWHO\LHDFRQGXLWFDQQRWEHXVHG
)LJXUH3=&:5&/*:LUHG5HPRWH([WHQVLRQ&DEOH
1(L1) 2(L2) 3
Power Wiring Connections
Lock nut
Conduit
mounting
plate
Conduit
Controller Options
Ceiling-concealed duct (high static) indoor units can be used with many LG-supplied wired controllers (sold separately). The wireless hand-
KHOGFRQWUROOHU0RGHO1R34:5+4)'%LVDOVRDQRSWLRQDODFFHVVRU\ZLWKXVHRIWKHZLUHGFRQWUROOHU
)LJXUHExterior View of Conduit Installation.
Indoor Unit Terminal Block
1(L1 ) 2 (L2)
GND
3
GRN /
YLW
BR
BL
RD
CN-REMO
YL
RD BK
Comm.
12V
Power
Ground
Wired Controller Connections
Controllers can connect to the indoor unit in one of two different
ways.
1. /*:LUHG5HPRWH([WHQVLRQ&DEOHZLWK0ROH[SOXJ3=&:5&
sold separately) that connects to the CN-REMO terminal on the
indoor unit PCB.
2. Field-supplied controller cable that connects to the indoor unit
WHUPLQDOEORFNPXVWEHDWOHDVW8/RU8/$:*
two-core, one-shield core, at least FT-6 rated if local electric and
building codes require plenum cable usage).
Verify the connectors are properly inserted.
C/BOX Cable (Plug type)
Extension cable
To Indoor Unit
CN-REMO
Terminal
TEMP
FAN
SPEED
OPER
MODE
)LJXUH:LUHG&RQWUROOHU&RQQHFWLRQVRQWKH,QGRRU8QLW7HUPLQDO
Block.
:KHQXVLQJ¿HOGVXSSOLHGFRQWUROOHUFDEOHPDNHVXUHWRFRQQHFWWKH\HOORZWR
\HOORZFRPPXQLFDWLRQVZLUHUHGWRUHG9SRZHUZLUHDQGEODFNWREODFN
JURXQGZLUHWHUPLQDOVIURPWKHUHPRWHFRQWUROOHUWRWKHLQGRRUXQLWWHUPLQDO
EORFNV
DUCT (HIGH STATIC) | 109