Multi F Engineering Manual

External Static Pressure
FOUR-WAY VAHU INDOOR UNITS
Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Model No. / Nominal Capacity
of Indoor Unit (Btu/h)
Airflow Rate / CFM Setting Value at (in. wg)
1
LVN180HV4
18,000
High 640 63 67 75 81 88 91 95
Mid 580 57 63 69 77 84 89 93
Low 480 51 59 65 73 80 87 91
LVN240HV4
24,000
High 710 67 71 79 85 92 94 97
Mid 640 63 67 75 81 88 91 95
Low 480 51 59 65 73 80 87 91
LVN360HV4
36,000
High 1,100 65 71 79 86 92 96 102 106 112
Mid 1,000 61 67 75 82 88 94 100 104 110 116
Low 900 57 63 71 78 84 92 98 102 108 114
1
8QOHVVRWKHUZLVHQRWHGYHUWLFDOKRUL]RQWDODLUKDQGLQJXQLWVDUH8/OLVWHGXSWRLQZJWRWDOVWDWLFSUHVVXUHLQFOXGLQJFRLOFDVHGXFWZRUNSUHVVXUHGURSDLUILOWHUDQGODUJHVWN:VL]HKHDWHU,QWHUQDOVWDWLF
pressure includes coil and case only.
2
Airflow rate (CFM) decreases by 3% per 0.1 in. wg.
3
Factory default setting is 0.3 in wg
4
Factory default setting is high static pressure
7DEOH Multi F Vertical-Horizontal Air Handling Unit External Static Pressure Setting Values Table.
Note:
,IWKH(63LVVHWLQFRUUHFWO\WKHDLUFRQGLWLRQLQJZLOOPDOIXQFWLRQ
To get the desired air flow and external static pressure combination, use the setting value from the table.
Using a setting value other than the values listed in the table will not provide the desired combination.
Capacity (kBtu/h [tons]) Flow Rate (CFM) Static Pressure Drop (in wg)
18 (1.5)
High (640) -0.04
Middle(580) -0.04
Low (480) -0.04
24 (2.0)
High (710) -0.04
Middle(640) -0.04
Low (480) -0.04
36 (3.0)
High (1100) -0.08
Middle(1000) -0.08
Low (900) -0.08
7DEOH Air Filter Static Pressure Drop Factors.
Capacity (kBtu/h [tons])
+HDWHU&DSDFLW\N:
3, 5 8, 10 15 20
18 (1.5)
480 480 Not Available Not Available
24 (2.0)
480 480 Not Available Not Available
36 (3.0)
900 900 900 900
7DEOH0LQLPXP$LUÀRZ&)0E\+HDWHU&DSDFLW\
'RQRWRSHUDWHZLWKOHVVWKDQWKHPLQLPXPDLUÀRZ,IDQDLUÀRZ
LVXVHGEHORZWKHPLQLPXPWKHUHLVDULVNRI¿UHZKLFKZLOO
lead to physical injury or death
Note:
'RQRWRSHUDWHZLWKOHVVWKDQWKHPLQLPXPDLUÀRZ,IDQDLUÀRZLV
XVHGEHORZWKHPLQLPXPWKHUHLVDULVNRIGDPDJHWRWKHSURGXFW
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
166 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual