Multi F Engineering Manual

General Information
ELECTRICAL CONNECTIONS
Multi F Systems:
Communication / connection (power) cable from the outdoor unit to the indoor unit for
OHQJWKVXSWRIHHWPXVWXVHDPLQLPXPRI$:*IRXUFRQGXFWRUVWUDQGHG
shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor
unit only), and must comply with applicable local and national codes.
:KHQWKHFRPPXQLFDWLRQFRQQHFWLRQSRZHUZLUHVEHWZHHQWKHLQGRRUXQLWDQG
RXWGRRUXQLWLV*5($7(57+$1IHHWXVH
A two (2) conductor wire for power (for each indoor unit).
A two (2) conductor wire for communication / ground (for each indoor unit).
Separate the power AT LEAST two (2) inches away from the communication /
ground wire (for each indoor unit).
All wiring is still minimum 18 gauge, stranded, shielded, or unshielded as cited
above (for each indoor unit).
Multi F MAX Systems:
All communication / connection (power) cable from the outdoor unit to the branch
GLVWULEXWLRQXQLWVPXVWEHDPLQLPXPRI$:*IRXUFRQGXFWRUVWUDQGHG
shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor
unit only), and must comply with applicable local and national codes.
Communication / connection (power) cable from the branch distribution unit(s) to
WKHLQGRRUXQLWVIRUOHQJWKVXSWRIHHWPXVWXVHDPLQLPXPRI$:*IRXU
conductor, stranded, shielded or unshielded (if shielded, it must be grounded to the
chassis of the outdoor unit only), and must comply with applicable local and national
codes.
:KHQWKHFRPPXQLFDWLRQFRQQHFWLRQSRZHUZLUHVEHWZHHQWKHEUDQFKGLVWULEXWLRQ
XQLWDQGLQGRRUXQLWLV*5($7(57+$1IHHWXVH
A two (2) conductor wire for power (for each indoor unit).
A two (2) conductor wire for communication / ground (for each indoor unit).
Separate the power AT LEAST two (2) inches away from the communication /
ground wire (for each indoor unit).
All wiring is still minimum 18 gauge, stranded, shielded, or unshielded as cited
above (for each indoor unit).
Insulation material as required by local code.
Rated for continuous exposure of temperatures up to 140°F.
Firmly attach the cable; provide slack but secure in a way to prevent external forces from being imparted on the terminal block.
:LULQJPXVWEHFRPSOHWHGZLWKRXWVSOLFHV
Communication / Connection (Power) Cable Specifications
)LJXUHTypical Multi F / Multi F MAX with
LGRED Outdoor and Indoor / Branch Distribution
8QLW:LULQJDQG&RPPXQLFDWLRQV&DEOH'LDJUDP
)RU:LULQJ/HQJWKV8SWR)HHW
Power Wiring, Ground,
Communication Cable
From Outdoor Unit
To Indoor Unit or from the
Outdoor Unit to the Branch
Distribution Unit
13/16”
GN/YL
GN/YL = (Ground, Yellow)
7/16" ± 1/8"
Two-Conductor
Power Cable
GN/YL
GN/YL = (Ground, Yellow)
Two-Conductor
Communication /
Ground Cable
Separate At Least
Two (2) Inches
13/16"
7/16" ± 1/8"
1(L1)
2(L2)
13/16"
7/16" ± 1/8"
3
)LJXUHMulti F with LGRED Outdoor Unit to
Indoor Unit, and Multi F MAX with LGRED Branch
'LVWULEXWLRQ8QLWWR,QGRRU8QLW:LULQJ'LDJUDPIRU
:LULQJ/HQJWKV*5($7(57+$1)HHW
8VHDFRQGXLWIRUWKHFRPPXQLFDWLRQVFRQQHFWLRQSRZHUFDEOHIURPWKHRXWGRRUXQLWWRWKHLQGRRUXQLWVDQGEUDQFKGLVWULEXWLRQXQLWV
Electrical interference my cause product malfunction.
1HYHUJURXQGWKHVKLHOGRIWKHFRPPXQLFDWLRQVFDEOHWRWKHLQGRRUXQLWIUDPHRURWKHUJURXQGHGHQWLWLHVRIWKHEXLOGLQJ*URXQGWKH
communications cable shield only at the outdoor unit. Improperly grounding this cable can cause communications errors.
7KHFRPPXQLFDWLRQVFRQQHFWLRQSRZHUFDEOHIURPWKHRXWGRRUXQLWWRWKHLQGRRUXQLWVEUDQFKGLVWULEXWLRQXQLWVPXVWEHVHSDUDWHGDQG
isolated from power wiring to the outdoor unit, computers, radio and television broadcasting facilities, as well as medical imaging equip
ment. Electrical interference my cause product malfunction.
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
WIRING CONNECTIONS | 207