Multi F Engineering Manual

DUCT (LOW STATIC) INDOOR UNITS
Measurements taken with no attenuation and units operating at full
load normal operating condition.
Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
Sound power levels are measured in dB(A).
Tested in anechoic chamber per ISO Standard 3745.
Model No.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
High Fan Speed
Medium Fan
Speed
Low Fan Speed
LDN097HV4
30 26 23
LDN127HV4
31 28 27
LDN187HV4 36 34 31
)LJXUHSound Pressure Level Measurement Location.
7DEOHSound Pressure Levels (dB[A]).
)LJXUHSound Pressure Level Diagrams.
Acoustic Data
4.9 ft.
Ceiling
6.6 ft.
Microphone
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
LDN097HV4 LDN127HV4
Octave Band Center Frequency (Hz)
2FWDYH%DQG6RXQG3UHVVXUH/HYHOG% ȝ3D
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximat e
Hearing
Threshold
LDN187HV4
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
80 | DUCT (LOW STATIC)
Multi F and Multi F MAX Indoor Unit Engineering Manual