Multi F Outdoor Unit Engineering Manual

•Neverapplylinevoltagepowertothecommunicationscableterminalblock.Ifcontactismade,thePCBsmaybedamaged.
•Alwaysincludesomeallowanceinthewiringlengthwhenterminating.Providesomeslacktofacilitateremovingtheelectricalpanels
whileservicing.
:Copper Wire
Terminate multiple power wires of
the same gauge to both sides.
Do not terminate two wires on
one side.
Do not terminate different gauge
wires to a terminal block.
Connecting the Power Wiring / Communications Cable
Best practice dictates using ring or spade terminals to terminate power wiring at the power terminal block. If ring terminals or spade clips are
not available, then:
•Do not terminate different gauge wires to the power terminal block. (Slack in the wiring may generate heat.)
•When terminating wires of the same thickness, follow the instructions demonstrated in the figures below.
Ifpowerwiresarenotproperlyterminatedandrmlyattached,thereisriskofre,electricshock,andphysicalinjuryordeath.
Ring Terminal
Power Wiring
Figure 93: Close up of a Typical Ring Terminal.
Figure 94: Close up of the Indoor Unit Terminal
Block.
•Firmly attach the wire; secure in a way to prevent external forces from being imparted on
the terminal block.
•Use an appropriately sized screwdriver for tightening the terminals.
•Do not overtighten the connections; overtightening may damage the terminals.
Figure 95: Proper and Improper Power Wiring Connections.
General Information
WIRING CONNECTIONS
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
WIRING CONNECTIONS | 221
Wiring Connections