LMN248HVT Installation Guide

44
Multi F Standard Wall-Mounted Indoor Unit
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MA
X
MUL
TI
F
MUL
TI
F
ELECTRICAL WIRING
Additional screens can be accessed by tabs on the main screen.
Additional screens include the following:
1. Cycleview (Figure 63): Graphic of internal components including:
Compressors showing actual speeds
EEVs
IDUs
Temperature and pressure sensors
Four-way reversing valve
2. Graph: Full screen graph of actual high and low pressures and high
and low pressure limits. A sliding bar enables user to go back in
time and view data.
3. Control FTN: Enables user to turn on IDUs in 1.8°F increments.
4. Useful Tab
Unit Conversion: Converts metric values to imperial values.
Actual inverter compressor speed
Target inverter compressor speed
Actual outdoor fan speed
Target outdoor unit fan speed
Actual superheat
Target superheat
Actual subcooler circuit superheat
Target subcooler circuit superheat
Main EEV position
Subcooling EEV position
Inverter compressor current transducer
value
Outdoor air temperature
Actual high pressure/saturation
temperature
Actual low pressure/saturation
temperature
Suction temperature
Inverter compressor discharge
temperature
Front outdoor coil pipe temperature
Back outdoor coil pipe temperature
Liquid line pipe temperature
Subcooler inlet temperature
Subcooler outlet temperature
Average indoor
unit (IDU) pipe
temperature
Inverter compres-
sor operation
indicator light
Liquid injection
valves’ operation
indicator lights
Hot gas bypass
valve operation
indicator light
Four-way
reversing valve
operation
indicator light
Pressure graph showing actual low
pressure and high pressure levels
Error code display
Operating mode indicator
Target high pressure
Target low pressure
Printed circuit board (PCB) version
Software version
Installer name
Model number of IDUs
Site name
Total number of connected IDUs
Communication indicators
IDU capacity
IDU operating mode
IDU fan speed
IDU EEV position
IDU room temperature
IDU inlet pipe temperature
IDU outlet pipe temperature
IDU error code
LG Monitoring View (LGMV) Diagnostic Software
LGMV software (PRCTSL1 and PRCTFE1) allows the service technician or commissioning agent to connect a computer USB port to the
outdoor unit’s main printed circuit board (PCB) using an accessory cable. The monitoring screen for LGMV allows the user to view the
following real time data on one screen (Figure 62):
Figure 62: MV Real-time Data Screen
Figure 63: MV Cycleview
Note:
Images on these pages are examples of LGMV screenshots. Actual images
may differ depending on the version of the software and the unit installed.
Self Diagnosis Functions