Mechanical Specications and Features
DUCT (HIGH STATIC) INDOOR UNITS
Ceiling-Concealed Duct (High Static) 
Indoor Unit
General
All LG indoor units are factory assembled, wired, piped, and provided 
with a control circuit board, fan, and motor. Ceiling-Concealed Duct 
(High Static) units are designed for high-speed air volume against an 
external static pressure up to 0.78″WG for the 24,000 Btu/h model; 
up to 0.55″WG for the 36,000 Btu/h model.
Coil
Indoor unit coils are factory built and are comprised of aluminum fins 
mechanically bonded to copper tubing. Each unit has two rows of 
coils, which are pressure tested at the factory. Each unit is provided 
with a factory installed condensate drain pan below the coil.
Refrigerant System
System is designed for use with R410A refrigerant. The refrigeration 
circuit is pressure-tested at the factory and shipped with a holding 
charge of helium gas. Refrigerant pipe connections are 45° flare, 
and all refrigerant lines from the outdoor unit to the indoor units must 
be field insulated.
Electrical
Each indoor unit is designed to operate using 208–230/60/1 power 
with voltage variances of ±10%.
Casing
The casing is designed to mount fully concealed above a finished 
ceiling. Casing is manufactured of galvanized steel plate. Cold sur-
faces of the unit are covered internally with a coated polystyrene in-
sulating material, and covered externally with sheet insulation made 
of ethylene propylene diene monomer (M-Class) (EPDM). External 
insulation is plenum rated and conforms to ASTM Standard D-1418. 
Hanger brackets are included on the casing to support the weight on 
four corners. Unit has a front horizontal supply air discharge outlet, 
and one dedicated rear horizontal return air inlet.
Fan Assembly and Control
The 24MBH (LHN248HV) indoor unit has one direct-drive Sirocco 
fan, while the 36MBH (LHN368HV) indoor unit has two direct-drive 
Sirocco fans. The fans are made of high strength ABS GP-2200 
polymeric resin that are statically and dynamically balanced. The 
fans are mounted on a common brushless digitally controlled (BLDC) 
motor with permanently lubricated and sealed ball bearings. The fan 
/ motor assembly is mounted on vibration-attenuating rubber grom-
mets. Fan speed is controlled using a microprocessor-based direct 
digital control algorithm. The indoor fan has Low, Med, High, and 
Auto settings for Cooling mode; and has Low, Med, High, and Auto 
settings for Heating mode. Each of the settings can be field-adjusted 
from the factory setting (RPM / ESP). The Auto setting adjusts the 
fan speed based on the difference between the controller setpoint 
and space temperature. 
Air Filter
Return air is filtered with a factory-supplied, removable, washable 
filter accessible from the rear of the indoor unit. High efficiency air 
filter options include a return filter box and an LG / Dynamic supplied 
air cleaner (both sold separately). 
Microprocessor Control 
The unit is provided with an integrated control panel to communicate 
with the outdoor unit. All unit operation parameters are stored in non-
volatile memory resident on the unit microprocessor. The micropro-
cessor controls space temperature through using the value provided 
by the temperature sensor within the indoor unit. The microprocessor 
control will activate indoor unit operation when the indoor room tem-
perature falls below or rises above a setpoint temperature, at which 
point, a signal is sent to the outdoor unit to begin the appropriate 
mode. The microprocessor will also provide self-diagnostics and auto 
restart functions. A field-supplied four-wire power / communications 
cable must be installed to connect the indoor unit(s) to the outdoor 
unit. 
Controls
The indoor unit controller of choice must be ordered separately. 
Communication between the indoor units and the outdoor unit is ac-
complished through 14 AWG, four-core, stranded and shielded power 
/ communication cable.
Condensate Lift/Pump
The indoor unit is provided with a factory installed and wired internal 
condensate lift/pump capable of providing a minimum 27.5 inch lift 
from the bottom surface of the unit. Drain pump has a safety switch 
to shut off the indoor unit if the condensate rises too high in the drain 
pan.
• Inverter (Variable speed fan)
• Internal drain pump
• Control lock function
• Auto operation
• Auto restart operation
• Dehumidifying function
• Two thermistor control
• External static pressure control
• Group control
• Self-diagnostics function
• Wired controller ordered separately
• Wi-Fi compatible
Features
Figure 152: Ceiling-Concealed Duct (High Static) Indoor Unit.
DUCT (HIGH STATIC) | 117
Ceiling-Concealed Duct (High Static)
Due to our policy of continuous product innovation, some specications may change without notication.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.