1.  Select and mark the area for the suspension or console bolts (use 
embedded inserts or anchor bolts in new buildings, and hole-in-
anchors in older buildings). 
2.  Drill the holes. 
3.  Add the set-anchor and the plate washer to the bolts (bolts must 
be at least 13/32 inches in diameter), and then insert the bolts 
into the installation area. 
4.  Add the plate washer, spring washer, and nut to secure the bolts 
into the installation area. 
5.  Position the indoor unit installation plates onto the bolts. Secure 
using nuts, plate washers, and spring washers. Adjust for level as 
necessary. 
• Unit must be installed correctly. Tighten the nuts and bolts to prevent the unit from falling and 
causing severe injury or death.
)LJXUH Preparing the Installation Area.
Install a canvas duct to the air outlet and air inlet so that vibration from the indoor unit does not 
FDUU\WRWKHGXFWRUFHLOLQJ$OVRDGGLQVXODWLRQWRWKHLQWHULRURIWKHGXFWDQGDSSO\DQWLYLEUDWLRQ
to the suspension bolts.
Preparing the Installation Area and Hanging the Indoor Unit Frame
)LJXUH Suspension Bolt Options.
)LJXUH Hanging the Indoor Unit.
M10 Nut
M10 SP. washer  
M10 washer  
X 4
X 4
(Field-
supplied)
X 4
M10 Nut
M10 SP. washer  
M10 washer  
X 4
X 4
X 4
(Field-
supplied)
'RQRWDSSO\IRUFHRUWZLVWWKHGUDLQKRVHLWZLOOOHDN
1/50~1/100 slope
Hanger distance
3.3~49.2 feet
Hanger Bracket
Maximum 
27-9/16 inches
Flexible drain hose
Insulation
Metal
clamp
Maximum 
11-13/16 inches
Installing the Drain System
• Drain piping must have downward gradient of at least 1/50 to 1/100; to prevent reverse flow, slope must 
not be straight up and down.
•  Do not damage the drain port on the indoor unit when connecting the field-supplied drain piping. 
• 'UDLQSLSLQJVSHFLILFDWLRQV
,QGRRU8QLW'UDLQ&RQQHFWLRQLQFKRXWVLGHGLDPHWHU
)LHOG6XSSOLHG'UDLQ3LSLQJ3RO\YLQ\OFKORULGHSLSLQJZLWKLQFKLQVLGHGLDPHWHUDQGSLSHILWWLQJV 
Drain Port 
Maintenance
Drain Pipe Support
Indoor unit
1/50~1/100mm
Maximum
27-9/16 inches
)LJXUHIndoor Unit Drain Piping.
)LJXUHDrain Piping Installation Dimensions.
Installation and Best Layout Practices
DUCT (HIGH STATIC) INDOOR UNITS
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ 
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
106 | DUCT (HIGH STATIC)
Multi F and Multi F MAX Indoor Unit Engineering Manual