Multi F Engineering Manual

MULTI 
F
MAX
MULTI 
F
Installation and Best Layout Practices
DUCT (HIGH STATIC) INDOOR UNITS
1.  To access system installer setting mode, press and hold the temperature increase and mode selection 
buttons simultaneously for approximately three (3) seconds. Choose setting code value “06” by press-
ing the mode selection button. 
2.  Use the temperature increase and decrease buttons to select the 
desired setting value. 
Setting Values 
3.  Press the on / off button to save the established settings. 
4.  To deactivate system installer setting mode after the settings have been established, press and hold 
the temperature increase and mode selection check buttons simultaneously for approximately three 
(3) seconds. If a button is not pressed for more than 25 seconds, the system installer setting mode 
will automatically deactivate.
• 6HOHFWWKHSRVLWLRQDIWHUYHULI\LQJGXFWZRUNDQGWKHH[WHUQDOVWDWLFSUHVVXUHRIWKHLQGRRUXQLW
• )DFWRU\VHWWRSUHVVXUHVHOHFWLRQ)+
7DEOHStatic Pressure Setting Table.
Pressure Selection
Function
=RQH6WDWH External Static Pressure Standard Value
01 V-H Variable High
02 F-H Fixed High
03 V-L Variable Low
04 F-L Fixed Low
TEM P
FA N
SPEED
OPER
MODE
Code 
Set Value
)LJXUHSelect Code and 
Set Value.
9+
)+
9/ 
)/
)LJXUHController External 
Static Pressure Setting Display.
External Static Pressure Control
To provide a required air flow rate that accounts for the external static pressure change, follow the steps 
below.
DUCT (HIGH STATIC) | 111