Multi F Engineering Manual

TWO-WAY VAHU INDOOR UNITS
0HFKDQLFDO6SHFL¿FDWLRQVDQG)HDWXUHV
Two-way Vertical-Horizontal Air  
Handing Indoor Unit
General
All LG indoor units are factory assembled, wired, piped, and pro-
vided with a control circuit board, fan, and motor. Vertical-Horizontal 
Air Handling units are designed for high-speed air volume against an 
H[WHUQDOVWDWLFSUHVVXUHXSWRƎ:*6XSSO\DLURSHQLQJLVIODQJHG
to accept field-installed ductwork that cannot exceed the external 
static pressure limit of the unit.
Coil
,QGRRUXQLWFRLOVDUHIDFWRU\EXLOWDQGDUHFRPSULVHGRIDOXPLQXP¿QV
mechanically bonded to copper tubing. Each unit has a minimum of 
two rows of coils, which are pressure tested at the factory. Each unit is 
provided with a factory installed condensate drain pan below the coil. 
Refrigerant System
System is designed for use with R410A refrigerant. The refrigeration 
circuit is pressure-tested at the factory and shipped with a holding 
charge of helium gas. Refrigerant pipe connections are 45° flare, 
and all refrigerant lines from the outdoor unit to the indoor units must 
be field insulated.
Electrical
Each indoor unit is designed to operate using 208–230/60/1 power 
with voltage variances of ±10%.
Casing
The casing is designed to mount fully concealed behind a wall 
or above a finished ceiling. Casing is manufactured of 22-gauge 
precoated metal and finished with a high-gloss baked enamel finish. 
Cold surfaces of the unit are covered internally with 1/2-inch polysty-
rene fiber insulation; inside surface of the pan assembly door access 
panel is treated with 1/2-inch polystyrene fiber insulation, encapsu-
lated on both sides. The access panel is sealed along the edges with 
reinforced foil-faced covering, all access panels also have gasket 
seals to minimize air leaks.
The two-way vertical-horizontal air handling unit can operate in one 
RIWZRDLUIORZFRQILJXUDWLRQVWKHYHUWLFDOXSIORZFRQILJXUDWLRQRU
horizontal (left) end discharge. Supply air is drawn from the top, and 
there is a dedicated bottom vertical return. Unit is also designed to 
accept an internal, optional LG electrical strip heater.
Fan Assembly and Control
The units have an integral fan assembly consisting of galvanized 
steel housing and a forward 
curve fan wheel. The fan 
motor is a brushless digitally 
controlled (BLDC) motor with 
permanently lubricated and 
sealed ball bearings. The fan 
/ motor assembly is mounted 
on vibration-attenuating rub-
ber grommets. Fan speed is 
controlled using a micropro-
cessor-based direct digital 
control algorithm. The indoor 
fan has Low, Med, High, and 
Auto settings for Cooling 
mode; and has Low, Med, 
High, and Auto settings for 
Heating mode. Each of the 
settings can be field-adjusted 
from the factory setting (RPM 
/ ESP). The Auto setting ad-
justs the fan speed to most 
effectively achieve setpoint. 
Filter Assembly
The unit includes a filter rack that can accept a field-supplied 16” x 
20” x 1” filter cartridge. The filter rack has a guide to assist in center-
ing the filters, and can be accessed from the front.
Microprocessor Control 
The indoor unit is provided with an integrated control panel to com-
municate with the outdoor unit. All unit operation parameters are 
stored in non-volatile memory resident on the unit microprocessor. 
The microprocessor controls space temperature through using the 
value provided by temperature sensors within the indoor unit. A 
field-supplied communication cable must be installed to connect the 
indoor unit(s) to the outdoor unit. 
Controls
The indoor unit controller of choice must be ordered separately. 
Communication between the indoor units and the outdoor unit is ac-
FRPSOLVKHGWKURXJK$:*IRXUFRUHVWUDQGHGDQGVKLHOGHGSRZHU
/ communication cable.
Condensate
The unit is designed for gravity draining of condensate.
• Inverter (Variable speed fan)
• Control lock function
• Auto operation
• Dehumidifying function
• Two thermistor control
• Group control
• External static pressure control
• Self-diagnostics function
• :LUHGFRQWUROOHURUGHUHGVHSDUDWHO\
Features
)LJXUH Multi F Vertical-Horizontal 
Air Handling Indoor Unit.
'XHWRRXUSROLF\RIFRQWLQXRXVSURGXFWLQQRYDWLRQVRPHVSHFL¿FDWLRQVPD\FKDQJHZLWKRXWQRWL¿FDWLRQ 
©/*(OHFWURQLFV86$,QF(QJOHZRRG&OLIIV1-$OOULJKWVUHVHUYHG³/*´LVDUHJLVWHUHGWUDGHPDUNRI/*&RUS
138 |  VERTICAL-HORIZONTAL