Multi F Four-Way Ceiling Cassette Service Manual
- 40 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Part 5. Trouble Shooting 
1.3 Error Indicator (Outdoor)
Outdoor Error
Ex) Error 21 (DC Peack)
1 Time 1 Time 1 Time
2 Times2 Times2 Times
1 Sec.
2 Sec. 2 Sec.
1 Sec. 1 Sec.
LED01G
(RED)
LED02G
(GREEN)
◑ : 
A light on the display panel is blink.
Error
Code 
Contents 
LED01G/M
(Red) 
LED02G/M
(Green) 
case of Error 
Outdoor
Status 
21 DC Link Peak (IPM Fault) 
2times ◑ 1times ◑
Over Rated Current 
Off 
22 CT 2 (Max CT) 
2times ◑ 2times ◑
Input Over Current 
Off 
23
DC Link Low Volt.
2times ◑ 3times ◑
DC Link Volt is below 140Vdc
Off 
DC Link High Volt. 
DC Link Volt is above 420Vdc 
25 Low Voltage/Over Voltage 
2times ◑ 5times ◑
Abnormal AC Volt Input 
Off 
26 DC Compressor Position Error 
2times ◑ 6times ◑
Compressor Starting Fall Error 
Off 
27 PSC/PFC Fault Error 
2times ◑ 7times ◑
Over Inverter PCB input current 
Off 
29 COMP Over Current 
2times ◑ 9times ◑
Over Inverter Compressor Current 
Off 
32 D-Pipe High 
3times ◑ 2times ◑
D-Pipe Temp. High 
Off 
35 Low Pressure Error 
3times ◑ 5times ◑
Excessive decrease of Low Pressure 
Off 
39 Communication Error
3times ◑ 9times ◑
Communication Error Between PFC
Micom and INV Micom
Off 
40 CT Sensor (Open/Short) 
4times ◑
○
CT Circuit Malfunction 
Off 
41 INV. D-Pipe Th Error 
4times ◑ 1times ◑
Open/Short 
Off 
43 High Pressure Sensor Error 
4times ◑ 3times ◑
Open/Short 
Off 
44 Outdoor Air Th Error 
4times ◑ 4times ◑
Open/Short 
Off 
45 Cond. Mid-Pipe Th Error 
4times ◑ 5times ◑
Open/Short 
Off 
46 Suction Pipe Th Error 
4times ◑ 6times ◑
Open/Short 
Off 
48 Cond. Out-Pipe Th Error 
4times ◑ 8times ◑
Open/Short 
Off 
51 Capacity Over 
5times ◑ 1times ◑
Over combination 
Off 
53 Signal Error (Indoor <-> Outdoor) 
5times ◑ 3times ◑
Communication Poorly 
Off 
54 3-Phase Wrong wiring
5times ◑ 4times ◑
3-Phase Wrong Wring of Outdoor Unit
(Reverse Phase/Omission of Phase)
Off 
60 EEPROM Check Sum Error 
6times ◑
○
Check Sum Mismatching 
Off 
61 Cond. Pipe Th High 
6times ◑ 1times ◑
Cond. Temp. High 
Off 
62 Heaksink Th High 
6times ◑ 2times ◑
Heatsink Temp. High 
Off 
65 Heaksink Th Error 
6times ◑ 5times ◑
Open/Short 
Off 
67 Outdoor BLDC Fan Lock 
6times ◑ 7times ◑
Outdoor Fan is not operation 
Off 
73 PFC Fault Error(S/W)
7times ◑ 3times ◑
Over Current of Outdoor Unit PFC
Off 