Multi F Four-Way Ceiling Cassette Service Manual
Part 5. Trouble Shooting 
- 86 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
26
DC Compressor
Position
• Compressor 
Starting fail error
• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM”, detection parts.
Display
code
Title Cause of error Check point & Normal condition
Is installation 
condition normal?
No 
Yes 
Yes 
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal 
 operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor 
 (0.438~0.628±7%)
2. Check insulation resistance between compressor 
 terminal and pipe (over 2MΩ)
→ Replace compressor if abnormality found
Are the resistance 
Between each phase and
 insulation resistance of Inverter 
compressor normal?
No 
Yes 
1. Check inverter PCB assembly U,V,W connector 
 connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
 (bad contact)
→ Reassemble if abnormality found
Is compressor 
Wire connection 
condition normal?
No 
Yes 
Check inverter PCB assembly IPM normality
→ Replace inverter PCB assembly
Is inverter PCB assembly normal?
No 
U, V, W
GND
<CT Sensing Check Point> 
Vdc
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
■ Error Diagnosis and Countermeasure Flow Chart