Multi F Four-Way Ceiling Cassette Service Manual
Part 5. Trouble Shooting 
- 88 -
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
29
Inverter compressor over
current
Inverter compressor input
current is over 30A
1. Overload operation 
(Pipe clogging/Covering/EEV defect/Ref. over-
charge)
2. Compressor damage(Insulation damage/Motor
damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
Display
code
Title Cause of error Check point & Normal condition
■ Error Diagnosis and Countermeasure Flow Chart
Is installation 
condition normal?
No 
Yes 
Yes 
Yes 
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal 
 operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
Yes
Is input voltage normal?
No 
Check 
L~N phase is 230V±15%
→ Check connection condition and wiring if power is 
 abnormal
Yes
Is inverter PCB assembly 
normal?
No 
Check inverter PCB assembly IPM normality
→ Replace inverter PCB assembly
Are the resistance 
Between each phase and
 insulation resistance of Inverter 
compressor normal?
No 
1. Check resistance between each terminal of compressor 
 (0.438~0.628±7%)
2. Check insulation resistance between compressor 
 terminal and pipe (over 2M
Ω)
→ Replace compressor if abnormality found
Is compressor 
Wire connection 
condition normal?
No 
1. Check inverter PCB assembly U,V,W connector 
 connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
 (bad contact)
→ Reassemble if abnormality found
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.