Multi F Engineering Manual

Refrigerant Piping Insulation
Field-installed vapor and liquid refrigerant piping lines must be
properly and completely covered in insulation (up to the indoor unit
piping connections). Any exposed piping will generate condensate or
will cause burns if touched. Insulation for this field-installed refriger-
ant piping must have a minimum heat resistance of 248°F.
Duct (low static) indoor units have been tested under and meet the
requirements of the “KS Conditions.” If the indoor unit is installed
and is operated at an extended period in a highly humid environment
(dew point temperature >73°F), however, condensate will form. To
prevent this phenomenon, install adiabatic glass wool insulation with
a thickness or 13/32 to 13/16 inches thick. Also, install glass wool
insulation on all indoor unit that are located in the ceiling plenum.
Drain Piping Insulation
Drain piping must have insulation a minimum of 7/32 inches thick.
DUCT (LOW STATIC) INDOOR UNITS
Installation and Best Layout Practices
)LJXUHInsulating the Piping.
Liquid Piping
Connection
Insulation for Refrigerant Piping
(Field-Supplied)
Vapor Piping Connection
Insulation
(Field-Supplied)
Clamp for Insulation
(Field-Supplied)
Ensure no gaps are present.
Overlap the Insulation at the
Connection
Insulation for Refrigerant Piping
(Field-Supplied)
Insulation for Field-Installed Piping
(Field-Supplied)
Insulating the Refrigerant and Drain Piping
Ensure all piping is insulated. Exposed piping can cause burns
if touched.