Multi F LMU540HV Installation Manual

Table Of Contents
12 Multi Air Conditioner
Installation of Indoor, Outdoor Unit
Multi Piping Type
Piping length and elevation
h2
A
B
C
D
h1
CAUTION: Capacity is based on standard length and maximum allowance
length is on the basis of reliability.
Unit : m(ft)
18k 50(164) 25(82) 3(10) 15(49) 7.5(25) 24k
24k 75(246) 25(82) 3(10) 15(49) 7.5(25) 33k
36k 75(246) 25(82) 3(10) 15(49) 7.5(25) 48k
Outdoor Unit
Capacity
(Btu/h class)
Max total length
of all pipes
(A+B)/(A+B+C)/
(A+B+C+D)
Max length of
each pipe
(A/B/C/D)
Min length of
each pipe
(A/B/C/D)
Max Elevation
between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
Max.Combination
of Indoor unit
(Btu/h class)
Indoor unit Capacity (Btu/h class)
Pipe Diameter
Unit : mm(inch)
Gas Liquid
9k 9.52(3/8) 6.35(1/4)
12k 9.52(3/8) 6.35(1/4)
18k 12.7(1/2) 6.35(1/4)