Multi F LMU540HV Installation Manual

Table Of Contents
28 Multi Air Conditioner
Installation
ESP Function
Out door
Room Temp
Total on
Central Run
Defrost Preheat
PQRCUCS0C
FAN
SPEED
MODE
Lo
Med
200
100
Setting the Low wind to 210 Setting the Medium wind to 175
TEMP
TEMP
1
Press the mode button and the temperature in-
creasing button(s) same time for three seconds.
2
Set the volume of each fan speed(Low, Medium, Hi)
by using the temperature control button. Press the
fan speed button to select the fan speed.
The value of E.S.P can be adjusted from 1 to 255.
3
If you press the On/Off button while setting the ESP
function, it will be canceled. (The picture on the left
side is the example of setting the Hi wind to ESP 10.)
4
Press the mode button and the temperature in-
creasing button (s) same time for three seconds.
Then the ESP setting will be activated after the
temperature display flashes three times.
E.S.P function is setting the volume of each fan speed. It is for the convenience of installation. It is
recommended that you should not use this function while using the remote controller.
EX)
h The E.S.P value is set at the proper value at the fac-
tory. So it is highly recommended that you should not
change the E.S.P value at your discretion.
Static pressure(mmAq)
Setting value
01234
Model name
Step(H/M/L)
8.5 CMM(300cfm) 75 84 94 104 114
7.5 CMM(265cfm) 69 77 88 99 110
6.5 CMM(230cfm) 62 71 83 95 106
9.5 CMM(335cfm) 82 90 99 109 118
8.5 CMM(300cfm) 75 84 94 104 114
7.5 CMM(265cfm) 69 77 88 99 110
15 CMM(530cfm) 90 97 105 114 122
13.5 CMM(477cfm) 82 90 99 109 119
11.5 CMM(406cfm) 75 84 93 103 114
AMNW09GB1A0
[LMDN095HV]
AMNW12GB1A0
[LMDN125HV]
AMNW18GB2A0
[LMDN185HV]