Multi F LMU540HV Installation Manual

Table Of Contents
36 Multi Air Conditioner
Installation
CAUTION : The supplied flexi-
ble drain hose should not be
curved, neither screwed. The
curved or screwed hose may
cause a leakage of water.
[Ceiling Concealed Duct/Ceiling Cassette Type]
Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent rever-
sal flow.
During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
The outside diameter of the drain connection on the in-
door unit is 32mm(1 1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe inner
diometes Ø 25mm(1 inch) and pipe fittings
• Connect the main drain pipe to the exterior and
leave it provisionally until the test comes to an
end.
Feed water to the flexible drain hose and check
the piping for leakage.
• Be sure to check the drain pump for normal op-
erating and noise when electrical wiring is com-
plete.
• When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Heat insulation material: Polyethylene foam
with thickness more than 8mm(5/16 inch).
Drain test
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
Flexible drain hose
MAX : 700 mm(27 9/16 inch)
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
1/50~1/100
Flexible drain hoseFlexible drain hoseFlexible drain hose
h The figure can be changed according to model.