LGRED Installation Manual

22
MULTI F / MULTI F MAX with LGRED Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
WITH
Clearance Requirements when Different Obstacles are Present, continued. (Unit: Inch)
PLACEMENT CONSIDERATIONS
Selecting the Best Location for the Outdoor Unit
Table 9: Ratio among H, A, and L.
If a stand is necessary, it must be contained (not
open frame) to prevent the discharge air from
short cycling.
LA
L
H
/+ 30 inches
1/2 H < L 40 inches
H < L 6HW6WDQGDV/+
³/´PXVWEHORZHUWKDQ³+´,IDVWDQG
is necessary, it must be contained (not
open frame) to prevent the discharge air
from short cycling.
Where there are obstacles on both suction
and discharge sides (discharge side obstacle
is higher than the outdoor unit).
Minimum 20"
Minimum 12"
Where there are obstacles above, and on both
suction and discharge sides (discharge side obstacle
is higher than the outdoor unit).
Maximum 20"
Minimum 12"
Minimum 40"
L
H
A
L
Minimum 40"
Minimum 40"
Maximum 20"
Minimum 12"
Where there are obstacles above, and on both
suction and discharge sides (discharge side obstacle
is lower than the outdoor unit).
H
Minimum 12"
Minimum 79"
Minimum 24"
Minimum 40"
Series installation.
Where there are obstacles on both suction
and discharge sides (discharge side obstacle
is lower than the outdoor unit).
Minimum 20"
Minimum 12"
Minimum 20
"
Maximum 20"
Minimum 40"
Obstacles above and on
the air discharge side.
Minimum 12"
Minimum 24"
Minimum 24"
Side-by-side series installation.