MULTI F / MULTI F MAX with LGRED Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
WITH
Table 12: Multi F MAX with LGRED Outdoor Unit Refrigerant Piping System Limitations.
Component
Size (Inches)
1/4 3/8 1/2 5/8 3/4
Elbow (ft.) 0.5 0.6 0.7 0.8 1.2
Y-Branch Kit (ft., Multi F MAX with
LGRED systems only)
1
1.6
Branch Distribution Unit (ft., Multi F
MAX with LGRED systems only)
8.2
Using Refrigerant Components
Field-supplied elbows are allowed as long as they are designed for
use with R410A refrigerant. The designer, however, must be cau-
tious with the quantity and size of fittings used, and must account
for the additional pressure losses in equivalent pipe length calcula-
tion for each branch. The equivalent pipe length of each elbow must
be added to each pipe segment.
Example of a Multi F MAX with LGRED System with Two Branch Distribution
Units
Example: LMU421HHV outdoor unit with six (6) indoor
units and two (2) branch distribution units connected.
ODU: Outdoor Unit.
IDU: Indoor Unit.
BD: Branch Distribution Unit(s).
A: Main Pipe.
B: Branch Pipe (Branch Distribution Unit[s] to Indoor Unit[s]).
Table 13: Multi F MAX with LGRED Piping Sizes.
Table 14: Equivalent Piping Length for Elbows, Y-branches, and Branch
Distribution Units.
Multi F MAX with LGRED Outdoor Unit Piping Length and Elevation
Limitations
5()5,*(5$176$)(7<67$1'$5'6
DEVICE CONNECTION LIMITATIONS
h1
C
Branch Pipe
Main Pipe
BD Unit
BD Unit
A
B
h2
Figure 23: Multi F MAX Refrigerant Piping
System Limitations.
Piping Main Pipe A (inch) Branch Pipe B
Liquid Ø3/8
Depends on the size
of the indoor unit piping
Gas Ø3/4
B
A
h2 IHHW
A
h3 IHHW
KIHHW
h1 IHHW
BDU Y-Branch
BDU
IDU
A
ODU
IDU
IDU
IDU
IDU
IDU
B
B
B
B
B
Pipe Length
(ELF = Equivalent
Length of pipe in
Feet)
7RWDOSLSLQJOHQJWKȉ$ȉ% IHHW
Main pipe (Outdoor
Unit to Branch Distri-
bution Units: A)
Minimum for Each (A)
Piping Segment
16.4 feet
0D[LPXPȉ$ IHHW
7RWDOEUDQFKSLSLQJOHQJWKȉ% IHHW
Branch pipe (Branch
Distribution Units to
Indoor Units: B)
Minimum 16.4 feet
Maximum IHHW
Elevation
Differential
(All Elevation
Limitations are
Measured in
Actual Feet)
If outdoor unit is above or below indoor unit (h1) IHHW
Between the farthest two indoor units (h2) IHHW
Between branch distribution unit and farthest
connected indoor unit(s) (h3)
IHHW
Between branch distribution units (h4) IHHW
Max. Combination
of IDUs
LMU361HHV = 48,000 LMU421HHV = 56,000 LMU480HHV = 65,000
1
.LWFRQWDLQVWZR<EUDQFKHVRQHIRUOLTXLGDQGRQHIRUYDSRU