The communications cable (connecting cable) from the outdoor unit to the indoor unit should be isolated from the electrical wiring of
H[WHUQDOGHYLFHVVXFKDVFRPSXWHUVHOHYDWRUVUDGLRDQGWHOHYLVLRQEURDGFDVWLQJIDFLOLWLHVDQGPHGLFDOLPDJLQJRIILFHV&RPPXQLFDWLRQ
problems can arise from electrical noise.
Do not install the power wiring to the outdoor unit and the power wiring / communications cable (connecting cable) to the indoor
units in the same conduit. These wiring / cables should have separate conduits that are placed a reasonable distance apart. Communi-
cation problems can arise from electrical noise.
Secure all field wiring connections with appropriate wire strain relief. Improperly securing wires will create undue stress on equipment
power lugs. Inadequate connections may generate heat, cause a fire and physical injury or death.
3URSHUO\WLJKWHQDOOSRZHUOXJV/RRVHZLULQJPD\RYHUKHDWDWFRQQHFWLRQSRLQWVFDXVLQJDILUHSK\VLFDOLQMXU\RUGHDWK
5HSODFHDOOFRQWUROER[DQGSDQHOFRYHUV,IFRYHUSDQHOVDUHQRWLQVWDOOHGVHFXUHO\GXVWZDWHUDQGDQLPDOVPD\HQWHUWKHRXWGRRUXQLW
causing fire, electric shock, and physical injury or death.
Connecting the Power Wiring / Communications Cable to the Outdoor Unit, continued.
Figure 76: Connecting the Power Wiring / Communications Cables to
the Outdoor Unit (LMU18~36CHV; LMU480, 540HV).
Power supply cabl
(1Ø, 208/230V)
Power Supply Cable
(1Ø, 208/230V)
Connecting cabl
(1Ø, 208/230V)
Connecting Cable
(1Ø, 208/230V)
Lock nut
(Field Supplied)
Indoor Unit A
Conduit
(Field Supplied)
Indoor Unit B
Indoor Unit C
Indoor Unit D
Conduit
Hole
WIRING
Power Wiring and Communications Cable Connections
Figure 77: Connecting the Power Wiring / Communications Cables to
the Outdoor Unit (LMU600HV).
Power Wiring
Terminal
Connecting
Cable Terminal
Cord Clamp
Cord Clamp
* Make sure the rubber bushes are
properly used in knock-out holes after
connecting the main power wiring.