MULTI F / MULTI F MAX with LGRED Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Multi F with LGRED Outdoor Unit Electrical Data
Table 2: Multi F with LGRED Electrical Data.
Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage Range
(Min. to Max.)
MCA MOP RFA
Compressor
Quantity
Compressor
Motor RLA
Outdoor Unit Fan
Motor
Indoor Unit
Fan Motor
kW FLA FLA
1.5 LMU180HHV
60 208 - 230 187 - 253
18.6 30 25 1 13 0.12 0.73 1.6
2 LMU240HHV 19 30 25 1 13 0.12 0.73 2.0
2.5 LMU300HHV 19.4 30 25 1 13 0.12 0.73 2.4
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.
The maximum combination for each outdoor unit is:
- 18,000 ODU (LMU180HHV): 12,000 IDU x 2
- 24,000 ODU (LMU240HHV): 12,000 IDU x 2 + 9,000 IDU
x 1
- 30,000 ODU (LMU300HHV): 12,000 IDU x 3